Specifications

Control Functions

Control methods

Open Loop Vector Control (Current Vector), V/f Control, PM Open Loop Vector Control (for SPM and IPM motors)

Frequency Control Range

0.01 to 400 Hz

Frequency Accuracy

(Temperature Fluctuation)

Digital input: within ±0.01% of the max. output frequency (-10°C to +50°C))
Analog input: within ±0.1% of the max. output frequency (25°C ±10°C)

Frequency Setting

Resolution

Digital input: 0.01 Hz
Analog input: 1/1000 of max. frequency

Output Frequency

Resolution

20 bit of maximum output frequency (parameter E1-04 setting)

Frequency Setting

Resolution

Main frequency reference: 0..10 V (20 kΩ) 10 bit, 4..20 mA (250 Ω) or 0..20 mA (250 Ω) 9-bit

Main speed reference : Pulse Train Input (max. 32 kHz)

Starting Torque

200% / 0.5 Hz (assumes Heavy Duty rating AC Motor of 3.7 kW or less using Open Loop Vector Control),

50% / 6 Hz (assumes PM Open Loop Vector Control)

Speed Control Range

1:100 (Open Loop Vector Control), 1:20 to 40 (V/f Control), 1:10 (PM Open Loop Vector Control)

Speed Control Accuracy

±0.2% in Open Loop Vector Control (25°C ±10°C) *

1

Speed Response

5 Hz in Open Loop Vector (25°C ±10°C) (requires Rotational Auto-Tuning)

Torque Limit

Open Loop Vector Control allows separate settings in four quadrants

Accel/Decel Time

0.0 to 6000.0 s (4 selectable combinations of independent acceleration and deceleration settings)

Braking Torque

q

Short-time decel torque*

2

: over 150% for 0.1/0.2 kW motors, over 100% for 0.4/ 0.75 kW motors, over 50% for 1.5 kW motors, and over 20% for

2.2 kW and above motors (overexcitation braking/High-Slip Braking: approx. 40%)

w

Continuous regen. torque: approx. 20% (approx. 125% with dynamic braking resistor option*

3

: 10% ED, 10 s, internal braking transistor)

V/f Characteristics

User-selected programs, V/f preset patterns possible

Main Control

Functions

Momentary power loss ride-thru, Speed search, Overtorque detection, Torque limit, 17-step speed (max), Accel/decel time switch, S-curve accel/decel,

3-wire sequence, Auto-tuning (rotational, stationary tuning for resistance between lines), Dwell, Cooling fan on/off switch, Slip compensation, Torque

compensation, Frequency jump, Upper/lower limits for frequency reference, DC injection braking at start and stop, Overexcitation braking, High slip

braking, PID control (with sleep function), Energy saving control, MEMOBUS comm. (RS-485/422 max, 115.2 kbps), Fault restart, Application presets,

DriveWorksEZ (customized function), Removable terminal block with parameter backup function...

Protection Function

Motor Protection

Motor overheat protection based on output current

Momentary Overcurrent Protection Drive stops when output current exceeds 200% of Heavy Duty Rating
Overload Protection

Drive stops after 60 s at 150% of rated output current (Heavy Duty Rating)*

4

Overvoltage Protection

200 V class: Stops when DC bus exceeds approx. 410 V

400 V class: Stops when DC bus exceeds approx. 820 V

Undervoltage Protection

Stops when DC bus voltage falls below the following levels:

Three-phase 200 V class: approx. 190 V, single-phase 200 V class: approx. 160 V, three-phase 400 V class: approx. 380 V, three-phase 380 V class:

approx. 350 V

Momentary Power Loss Ride-Thru

Stops after approx. 15 ms (default). Parameter settings allow the drive to continue running if power loss lasts for up to approx. 2 s *

5

Heatsink Overheat Protection

Protection by thermistor

Braking Resistance Overheat

Protection

Overheat sensor for braking resistor (optional ERF-type, 3% ED)

Stall Prevention

Separate settings allowed during acceleration, and during run. Enable/disable only during deceleration.

Ground Fault Protection

Protection by electronic circuit *

6

Charge LED

Charge LED remains lit until DC bus has fallen below approx. 50 V

Operating Environment

Area of Use

Indoors

Ambient Temperature

-10°C to +50°C (open chassis), -10°C to +40°C (NEMA Type 1)

Humidity

95 RH% or less (no condensation)

Storage Temperature

-20°C to +60°C (short-term temperature during transportation)

Altitude

Max. 1000 m (output derating of 1% per 100 m above 1000 m, max. 3000 m)

Shock

10 to less than 20 Hz (9.8 m/s2) max., 20 to 55 Hz (5.9 m/s2) max.

Safety Standard

UL508C, EN954-1 Cat. 3, IEC/EN61508 SIL2

Protection Design

IP20 open-chassis, NEMA Type 1 enclosure

*

1

Speed control accuracy may vary slightly depending on installation conditions or motor used.

*

2

Momentary average deceleration torque refers to the deceleration torque from 60Hz down to 0 Hz. This may vary depending on the motor.

*

3

If L3-04 is enabled when using a braking resistor or braking resistor unit, the motor may not stop within the specifi ed deceleration time.

*

4

Overload protection may be triggered at lower levels if output frequency is below 6 Hz.

*

5

Varies by drive capacity. Drives smaller than 7.5 kW (CIMR-VA2A0004/CIMR-VA4A0023) require a separate Momentary Power Loss Recovery Unit to continue operating during a momentary power loss of 2 s.

*

6

Protection may not be provided under the following conditions as the motor windings are grounded internally during run:

• Low resistance to ground from the motor cable or terminal block.
• Drive already has a short-circuit when the power is turned on.

Rotational Auto-Tuning must be performed to achieve the performance described with Open Loop Vector Control.