Specifications – Crompton Controls CIMR-VC4A0001BAA User Manual
Page 4
4
YASKAWA V1000
Specifications
Voltage class
Single-phase 200 V
Inverter model CIMR-VCBA*
1
0001
0002
0003
0006
0010
0012
00018*
6
Inverter output
Motor output kW at normal duty*
2
0.18
0.37
0.75
1.1
2.2
3.0
–
Motor output kW at heavy duty *
2
0.1
0.18
0.55
0.75
1.5
2.2
4.0
Rated output current at normal duty [A]*
3
1.2
1.9
3.3
6
9.6
12
–
Rated output current at heavy duty [A]
0.8*
4
1.6*
4
3.0*
4
5.0*
4
8.0*
5
11.0*
5
17.5*
5
Overload
125% for 60 sec normal duty, 150 % for 60 sec
at heavy duty from inverter rated output current
Rated output power at normal duty [kVA]*
0.5
0.7
1.3
2.3
3.7
4.6
-
Rated output power at heavy duty [kVA]*
0.3
0.6
1.1
1.9
3.0
4.2
6.7
Max. output voltage
Three-phase 200 to 240 V (proportional to input voltage)
Max. output frequency
400 Hz
Inverter
input
Rated input voltage
Single-phase 200 to 240 V, -15% to +10%
Rated input frequency
50/60 Hz, ±5%
* based on input voltage 220 V
Voltage class
Three-phase 200 V
Inverter model CIMR-VC2A
0001
0002
0004
0006
0010
0012
0020
0030
0040
0056
0069
Inverter output
Motor output kW at normal duty*
2
0.18
0.37
0.75
1.1
2.2
3.0
5.5
7.5
11.0
15.0
18.5
Motor output kW at heavy duty*
2
0.1
0.2
0.4
0.75
1.5
2.2
4.0
5.5
7.5
11.0
15.0
Rated output current at normal duty [A]*
3
1.2
1.9
3.5
6.0
9.6
12.0
19.6
30.0
40.0
56.0
69.0
Rated output current at heavy duty [A]
0.8*
4
1.6*
4
3.0*
4
5.0*
4
8.0*
5
11.0*
5
17.5*
5
25.0*
5
33.0*
5
47.0*
5
60.0*
5
Overload
120% for 60 sec at normal duty, 150% for 60 sec at heavy duty from inverter rated output current
Rated output power at normal duty [kVA]*
0.5
0.7
1.3
2.3
3.7
4.6
7.5
11.4
15.2
21.3
26.3
Rated output power at heavy duty [kVA]*
0.3
0.6
1.1
1.9
3.0
4.2
6.7
9.5
12.6
17.9
22.9
Max. output voltage
Three-phase 200 to 240 V (proportional to input voltage)
Max. output frequency
400 Hz
Inverter
input
Rated input voltage
Three-phase 200 to 240 V, -15% to +10%
Rated input frequency
50/60 Hz, ±5%
* based on input voltage 220V
Voltage class
Three-phase 400 V
Inverter model CIMR-VC4A
0001
0002
0004
0005
0007
0009
0011
0018
0023
0031
0038
Inverter output
Motor output kW at normal duty*
2
0.37
0.75
1.5
2.2
3.0
4.0
5.5
7.5
11
15.0
18.5
Motor output kW at heavy duty*
2
0.18
0.37
0.75
1.5
2.2
3.0
4.0
5.5
7.5
11.0
15.0
Rated output current at normal duty [A]*
3
1.2
2.1
4.1
5.4
6.9
8.8
11.1
17.5
23.0
31.0
38.0
Rated output current at heavy duty [A]*
5
1.2
1.8
3.4
4.8
5.5
7.2
9.2
14.8
18.0
24.0
31.0
Overload
120% for 60 sec at normal duty, 150% for 60 sec at heavy duty from inverter rated output current
Rated output power at normal duty [kVA]*
0.9
1.6
3.1
4.1
5.3
6.7
8.5
13.3
17.5
23.6
29.0
Rated output power at heavy duty [kVA]*
0.9
1.4
2.6
3.7
4.2
5.5
7.0
11.3
13.7
18.3
23.6
Max. output voltage
Three-phase 380 to 480 V (proportional to input voltage)
Max. output frequency
400 Hz
Inverter
input
Rated input voltage
Three-phase 380 to 480 V, -15% to +10%
Rated input frequency
50/60 Hz, ±5%
* based on input voltage 400 V
*
1
Drives with a single-phase power supply input have three-phase output. Single-phase motors cannot be used.
*
2
The motor capacity (kW) refers to a YASKAWA 4-pole, 60 Hz, 200 V motor. The rated output current of the drive output amps should be equal to or greater than the motor rated current.
*
3
at 2 kHz carrier frequency without derating
*
4
at 10 kHz carrier frequency without derating
*
5
at 8 kHz carrier frequency without derating
*
6
only heavy duty available