beautypg.com

Interlocks – Crompton Controls 3DPM1CHS/10 User Manual

Page 15

background image

15

Interlocks

The two internal relays controlling the starting (RL1) and braking (RL2) provide in initial

degree of interlocking. The normally closed on the first relay feeds the common on the

second so the outputs 18 and 28 cannot be on at the same time. Electrical interlocks are

also used on the main and DC contactors. However if the interlocking is bypassed for

some reason then the AC and DC contactors energised together put a direct short circuit

across two phases and supply fuse size will determine the amount of damage.

If several brake modules are used with a common control circuit it is important to

maintain interlocks across all the units. Use volt free relay contacts in the common circuit

from relays connected to terminal 18 on each module.

General Notes

Star Delta run up times of approx 15 sec or more could result in the overload tripping.

Star Delta connections are important easy to have the motor start and run but not dc

inject if the 6 leads are not correctly marked or wired.

Inertia can result in the need to increase the amount of dc current. E.g. Disc sanders,

band saws, and high-speed routers.

Mechanical damage can occur with very high levels of dc injection.

The motor resistance will change with temp up to 30% from cold to hot, reducing

braking as the motor warms.

Bad connections can cause severe damage to contactors –old machines have old

motors, wiring and starters. Sawdust and woodchips inside contacts is a prime cause of

bad connections.

More than one motor can be dc injected using the same thyristor/diode power assembly

if all can be stopped together.

Multi motor machines (tennoners) can have individual start buttons but one common

stop which will dc inject all motors running or stationary.

Aux block on the main contactor has to be moved to allow the starter to be wired. If

not put back in place this may result in no braking i.e. the brake contactor doesn’t

operate.

Check connections to the motor if the brake contactor is operating but the motor is not

braking.

This can be quickly done by measuring the winding resistance across the diode M1 to

M2 while operating the brake contactor by hand to make the circuit.