beautypg.com

Clearances from combustibles – Drolet COMPAK EPA EXEMPT 45109A User Manual

Page 7

background image

6

CLEARANCES FROM COMBUSTIBLES

It is of outmost importance that the clearances to combustible materials be scrupulously
respected upon installation of the stove you have selected. Refer to the tables below :


Single pipe / Double pipe

A

B

C

D

E

F

29”

30”

39”

34-3/4”

22”

32”


Floor to ceiling height must be at least 7' (84") in all cases.

The clearance between the flue pipe and a wall are valid only for vertical walls and for
vertical flue pipe.

The flue pipe must not go through roof trussing, an attic, a wardrobe, a floor, a
combustible partition, or similar spaces.

A flue pipe crossing a combustible wall must have a minimum clearance of 18".

To reduce flue pipe clearances from combustible materials, contact your local safety
department.

For reduced clearances refer to NFPA 211 table 9-6.6.1.