4. Smoke detectors must always be mounted on

the ceiling, as close to the centre of the room as
possible. According to DIN EN 14676, a distance
of at least 0.5 m must be maintained from all
furnishings on the ceiling and from the walls.
If the smoke detector is installed in an attic,
it must be installed, at a roof slope of
a. of up to 20° , recessed at least 0.2 m – 0.5 m

from the peak of the roof. The smoke
detector may be mounted both to the side
and directly on the top of the roof.

b. of more than 20° horizontally and recessed

by 0.2 m – 0.5 m.

Installation sites to avoid
Do not install smoke detectors:
1. Do not install smoke detectors in areas prone to

drafts, e.g. near air intakes for air conditioners
and ventilation.

2. In bathrooms, shower rooms or in rooms where

the temperature exceeds 39° C or falls below 0° C.

3. Do not install in the peak of a room since smoke-

free air can collect there in the event of a fire.

4. Less than 0.5 m distance from the wall if it is

mounted on the ceiling.

5. In kitchens, garages, washrooms or

furnace/boiler rooms, since vapours from