3. DIMENSIONS


The ATxBlock transmitter is intended for in head mounting. Its drawing is presented

in figure below:

ATxBlock Dimensions

4. ORDERING DETAILS


TYPE

DESCRIPTION

Product

ATx

Universal Temperature Transmitter 2-wire system

Isolation

Iso

Isolation 1500 Vac Input, Output and Power supply

N

None

Mounting

B

Head Mounting

R

DIN Rail Mounting

Output

D

4 ~ 20 mA dc

V

0 ~ 10 V dc

Accessories

+C

Configurator along with software

N

None, factory setting

Example: ATx > Iso > B > D > N

5. CONNECTIONS



5.1 Connector Specification

Insulating material: Polyamide, self-extinguishing to UL 94, V-0

Connection wire cross section: 0,14-1,5 mm² / AWG 28-14

Screw tightening torque: 0,8 Nm / 7.0 lb-in

Terminal block: CuZn