ABUS Technologies LPI-T Loop Powered Indicator User Manual
Page 7

ABUS TECHNOLOGIES INC.
7
LPI-T
6. CONFIGURATION
Configuration Process
Note: In the following description, “A” denotes the left button, “B” denotes the right button, and “A+B”
denotes pressing the left button and the right button at the same time.
1. Power On
After the digital display was connected to the current circle 4 ~ 20mA, the
name of the manufacturer is displayed, and further enters into the interface of
display.
2. Zero-point (value to be displayed)
Press button “A+B”, unit is displayed.
“A+B” menu item for setting.
“A” to move the cursor; “B” to change the value that the cursor points to. For
example -100.0Kpa.
“A+B” to confirm and store setting and return to the menu item.
3. Span (value to be displayed for 20mA)
Press button “A”, unit is displayed.
“A+B” menu item for setting.
“A” to move the cursor, “B” to change the value that the cursor points to. For
example -100Kpa.
“A+B” to confirm and store setting and return to the menu item.