Owner’s manual, Fresh air for combustion and ventilation, Continued – Desa CGP6L User Manual

Page 5

background image

5

103547

OWNER’S MANUAL

FRESH AIR FOR
COMBUSTION AND
VENTILATION

Continued

Or

Remove

Door into
Adjoining

Room,

Option 3

Ventilation Grills

Into Adjoining Room,

Option 2

12"

12"

Ventilation

Grills

into Adjoining

Room,

Option 1

Figure 2 - Ventilation Air from Inside Building

Figure 3 - Ventilation Air from Outdoors

Outlet
Air

Ventilated
Attic

Outlet
Air

Inlet
Air

Inlet Air

Ventilated

Crawl Space

To

Crawl

Space

To Attic

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation
grills or ducts. You must provide two per-
manent openings: one within 12" of the
ceiling and one within 12" of the floor.
Connect these items directly to the outdoors
or spaces open to the outdoors. These spaces
include attics and crawl spaces.

IMPORTANT:

Do not provide openings

for inlet or outlet air into attic if attic has a
thermostat-controlled power vent. Heated
air entering the attic will activate the power
vent.