MAINTENANCE

FIGURE 15

There is no scheduled maintenance required for Nexen’s EN40 Electro-Pneumatic Convertor.

TROUBLESHOOTING

OPERATIONAL CHECK

1. Remove Gauge Port Plug, and install a suitable

air pressure gauge.

2. Apply Psup to inlet port (See Table 1).

CLEANING FIXED ORIFICE

NOTE: If dirt or foreign particles are present in Fixed
Orifice, check condition of Pre-filter and Coalescing
filter. These filters must be kept clean and properly
maintained to prevent clogging of Fixed Orifice.

1. Remove Fixed Orifice Housing (See Figure 14).

2. Remove O-ring and Orifice Plate (See Figure 15).

3. Clean Fixed Orifice Housing Air Passage.

4. Passing a thin wire through hole in Orifice Plate,

clean Orifice Plate Air Passage.

CAUTION

Do not use cleaning solvents to clean o-
rings. Clean o-rings with a clean dry cloth,
then apply a thin coat of o-ring lubricant

to the o-rings.

5. Install Orifice Plate and clean O-rings into Fixed

Orifice Housing.

6. Install Orifice Housing onto EN40.

FIGURE 14

PARTS LIST

3. Vary electrical signal to “EN40” within the range of

4-20mA, DC.

a) If pressure does not vary directly with signal,
reverse electrical leads.

b) If pressure is slow to react to changes in
signal, clean Fixed Orifice.


Fixed
Orifice
Housing

O-ring

Orifice
Plate

Item

Description

EN40-1A EN40-1B EN40-2B EN40-1D

1

Upper Diaphragm Assembly

2720

2720

2720

2720

2

Lower Diaphragm Assembly

2721

2722

2722

2723

3

Orifice Plate

2662

2662

2662

2662

4

Coil Assembly with Poppet

2666

2666

2666

2666