VERSATEC BASE SERIES INSTALLATION MANUAL
Electrical Data cont.
5-Speed ECM Motor
HACR circuit breaker in USA only
Model
Rated
Voltage
Voltage
Min/Max
Compressor
Blower
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
MCC
RLA
LRA
015
208-230/60/1
198/253
9.2
5.9
29.0
4.1
10.0
11.5
15
265/60/1
238/292
7.8
5.0
28.0
3.6
8.6
9.8
10/15
018
208-230/60/1
198/253
10.4
6.7
33.5
4.1
10.8
12.5
15
265/60/1
238/292
8.7
5.6
28.0
3.6
9.2
10.6
10/15
024
208-230/60/1
198/253
13.0
7.4
43.0
4.1
11.5
13.4
20
265/60/1
238/292
12.6
6.7
46.0
3.6
10.3
12.0
15
208-230/60/3
187/253
13.0
5.9
63.0
4.1
10.0
11.5
15
460/60/3
414/506
6.0
2.9
30.0
2.1
5.0
5.7
10/15
030
208-230/60/1
198/253
17.5
9.4
54.0
4.1
13.5
15.9
25
265/60/1
238/292
14.0
8.0
46.0
3.6
11.6
13.6
20
208-230/60/3
187/253
13.5
6.6
63.0
4.1
10.7
12.4
15
460/60/3
414/506
6.4
3.2
30.0
2.1
5.3
6.1
10/15
036
208-230/60/1
198/253
20.5
11.6
74.0
4.1
15.7
18.6
30
265/60/1
238/292
17.7
9.9
67.0
3.6
13.5
16.0
25
208-230/60/3
187/253
13.5
7.4
68.0
4.1
11.5
13.4
20
460/60/3
414/506
7.1
3.8
34.0
2.1
5.9
6.9
10/15
042
208-230/60/1
198/253
25.0
13.0
88.0
7.6
20.6
23.9
35
208-230/60/3
187/253
14.5
8.6
68.0
7.6
16.2
18.4
25
460/60/3
414/506
7.7
4.2
34.0
4.0
8.2
9.3
10/15
048
208-230/60/1
198/253
24.5
15.7
84.0
7.6
23.3
27.2
40
208-230/60/3
187/253
17.5
11.0
88.0
7.6
18.6
21.4
30
460/60/3
414/506
8.0
5.6
44.0
4.0
9.6
11.0
15
060
208-230/60/1
198/253
33.0
21.1
105.0
7.6
28.7
34.0
50
208-230/60/3
187/253
22.0
12.9
88.0
7.6
20.5
23.7
35
460/60/3
414/506
12.0
6.7
55.0
4.0
10.7
12.4
15
070
208-230/60/1
198/253
36.0
23.0
130.0
7.6
30.6
36.4
50
208-230/60/3
187/253
24.6
14.3
110.0
7.6
21.9
25.5
35
460/60/3
414/506
11.5
7.1
55.0
4.0
11.1
12.9
20
10/03/12