REFCO GOBI User Manual
Page 5

Wiring Connections
Connect the ground, live and neutral wire from the supply cable of the GOBI pump to
the supply terminals (see Fig.6)
This product must be connected using a switch with contact separation in all poles that
provide full disconnection from the power supply under over-voltage categories III. A
fuse non time delay (rated 250V 1A), shall be fitted into the line, supply side (see
).
Fig.6
Alarm Contacts
Volt Free Break On Fault connection is rated 5
amps 1250VA. It may be necessary to use a
contactor if the air handler supply is to be switched.
Cable Connections
1 GREEN/ YELLOW
EARTH
E
2 BLACK
LIVE
L
3 WHITE
NEUTRAL
N
4 VIOLET
Alarm contact
5 VIOLET
Alarm contact
Wire Colour
Connect
Symbol
E
L
N
POWER SUPPLY
CONTROL
CIRCUIT
1A
FUSE
1
2
3
4
5
Fig.6
Set-up & Test
Warning
.
1.
- the pump is live during testing
2. Remove the GOBI cover.
3. Half fill the condensate collection tray with
clean tap water - The pump will start on low
power. It may be noisy whilst air is purged
from the system.
4. Continue to add water until the sensor is fully
submerged - The pump will switch to full
power and the alarm contacts will open.
5. Allow the GOBI to remove the water from
the collection tray - The pump will stop and
the alarm contacts will close.
6. Re-fit the GOBI cover.
Coil Cleaning
Do not allow the pump to collect or
operate with cleaning chemicals in the
system.
Disconnect ALL power supplies.
1.
2. Remove air-handler cover, GOBI cover
and condensate collection tray.
3. Follow manufacturers instructions but
collect chemicals in a separate container.
4. Flush the system with clean water.
5. Re-fit condensate collection tray, GOBI
cover and air-handler cover.
4
GB