12

activated only when the AC main

voltage is within the range of LO

(low) and HI(high). In this screen,

press Enter-key to enter the

following steps for LO/HI voltage

setting.

B. The cursor (→) will pop up to

indicate the item newly selected.

Press Enter-key to get the item of

LO or HI range the user want to

adjust.

C. Use Up or Down-key to adjust

the voltage (changing 1V by

every press). LO (low

rang):176V+/- 20V, HI(high

range):253V+/- 20V).

D. Once the value is confirmed,

press Enter-key again to save

the data.

13

Output Voltage & Frequency Adjust

A. In this screen, press Enter-key to

enter the following steps for

output voltage and frequency

adjustment.

B. The cursor (→) will pop up to

indicate the output voltage and

frequency newly selected.

C. Use Up or Down-key to adjust

the output voltage (220V, 230V,

and 240V ). Press Enter-key to

confirm voltage and then the

cursor will move to frequency

selection. The output frequency

(50Hz or 60Hz) can be adjusted

by the same key operation.

D. Once the correct voltage is

selected, press Enter-key again

to save the selection.