12. Technical specifications 

   

Input Characteristics 

 

Capacity:

   

Voltage Range: 

   

Phases: 

   

Frequency Range: 

         

Termination 

terminal block 

45 KVA 

380Y/220 Volt, +15% to ‐ 15% at 50 Hz for regulation. 

Three phases‐4 wire ,Wye connection(R,S,T,N,G) 

47‐53Hz for 50Hz models +/‐3Hz 

terminal board 

Output Characteristics 

 

Voltage:     

Phases:     

Voltage Range:     

 

Frequency Range:     

 

Load Regulation:   

Harmonic Distortion:     

Efficiency:     

Overload:   

Wav e form:     

Insulation Resistance: 

Technology: 

 

By‐pass Switch 

Cooling: 

Termination 

380Y/220 Volt 

Three phases‐4 wire ,Wye connection(U,V,W,N,G) 

Regulated to ±1~2% of nominal voltage with an input voltage range of +15 

to –15% 

50Hz, for every 1% change in input frequency the output voltage will change by 

1% in the same direction. 

5%, no load to full load 

non 

97% at full load. 

For 1 minutes 100%,for 30 minutes 125%,for 60 minutes 100%. 

Sinewave 

5 megaohms from winding to core measured at 500Vdc 

This technique usesthe combination of a motor driven variable transformer with 

buck‐boost transformer technology. 

input power directly to load, bypassing the voltage regulator. 

fan assisted 

terminal board 

Environmental 

 

Audible Noise:     

Ambient Temperature:     

 

Operating Altitude:     

Operating Humidity:   

Heat Rejection: 

 

Less than 65 dBA at 1.5 metre 

0° to 40 °C Operating, 

10° to 90 °C Storage 

3,000 metre without derating 

90% relative (non‐condensing) 

At full load, 10% of VA rating x 3.41. 

 

 

 

13‐ Machine schematic view/outline