7.4 Interpreting UPS messages

Troubleshooting procedures described here give simple instructions in determining UPS
malfunctions.

Start the troubleshooting procedure if you witness any alarm indication on the control panel.

Alarm indicators

The UPS gives the following audible alarms:

z If UPS is on battery and the ON BATTERY LED is on, UPS will beep every 5 seconds.

z If the battery capacity is low and the ON BATTERY LED is flashing, the UPS will beep

twice every 5 seconds.

z If UPS is on bypass and the BYPASSED LED is on, UPS will no beep.

z If UPS has an internal fault and the ALARM LED is on, the UPS will give a constant

audible alarm displaying the cause on the LCD display.

Silencing an alarm

By pressing any of the three buttons on the front panel, the alarm can be turned off, except
when the battery is low, which will cause the alarm to resound.

On the LCD display, you can also choose silent alarm mode which will not warn you of any
malfunction audibly.

27

7.5 Trouble shooting

Displayed on LCD

Audible Alarm Alarm Description

What You Should Do

Output Overload

Two Beeps per
second

The UPS is overloaded (in
Line Mode). Your
equipment needs more
power than the UPS can
provide. The UPS operates
in bypass.

Shut off the least important
equipment connected to the
UPS. If this solves the
overload problem, the UPS
will switch from bypass back
to normal operation.

Battery Test

No Beeps

The UPS is doing a battery

test.

No action needed. The UPS

will return to normal operation

when it successfully completes

the battery test.

Over-Charge Constant

beep

Batteries are
overcharged.

Turn off protected loads. Turn
off UPS and call your local
dealer

Low Battery

2 beeps every
5seconds

The unit is operating on
Battery Power and will shut
down soon due to very low
battery voltage

The unit will restart
Automatically when
acceptable power returns.

On-Battery

Once every 5
seconds

The unit is operating on
Battery Power.

Save your data and perform a
controlled shutdown.

Charger Failure

Constant beep

Charger has failed.

Phone the local dealer

Over-Temperature

Constant beep

High ambient Temperature.

Make sure the unit’s fans and
vent holes are not blocked, and
make sure the ambient
surrounding temperature is not
above 40 degree C. If these
conditions did not solve the
problem, call your service
representative.

Output Short

Constant beep

Output short circuit

Call the Local dealer

High output Voltage

Constant beep

High output voltage

Call the Local dealer

Low Output Voltage

Constant beep

Low output voltage

Call the Local dealer

Bus Fault

2 Beeps per
second

High internal DC bus
Voltage.

Turn off protected loads. Turn
off UPS and call your local
dealer

Site wiring Fault

1 Beep per
second

Voltage detected Between
Neutral and Ground

UPS mains connector polarity
Wrong. Rotate the connector
(Schuko). UPS installed to
mains supply without ground.
See page 15 on how to disable
the Site wiring alarm

Line abnormal

1 Beep per
second

Wrong AC Line backed up
during auto restart