Periodic Test:
1. Every thirty (30) days the ODORATOR should be operated with the
power switch on and while not hooked up to a gas supply.
2. Wait about 30 seconds and then position the nose about 3/4 inch (20
mm) above the exhaust port and sniff the exhaust.
3. If no odor is detected, turn the ODORATOR “OFF”. The ODORATOR
has not absorbed the odorant and is usable.
4. If an odor is detected, turn the ODORATOR “OFF” and send it to the
nearest Heath Repair Center (Regional Office) listed on page 20. The
odor is an indication that the ODORATOR has absorbed the odorant
and must have its internal tubing replaced and gas flow components
cleaned.
The forms on pages 8-11 are provided to document the Periodic Tests
and are as a courtesy only. Company procedures will define how records
are kept and in what format.
Calibration:
For regulatory compliance, instrument calibration and maintenance a
factory calibration is recommended every 12-15 months from the date
of the previous factory calibration. Only Heath factory or factory trained
personnel should perform ODORATOR calibration. Factory recognized
labels and seals maintain warranty.
Refer to page 20 for Heath repair and calibration centers.