Chapter i, Dp-ir system specifications – Heath Consultants Detecto Pak-Infrared (DP-I) User Manual
Page 7
102105-0 DP-IR MANUAL REV M
Page 7 of 35
Detection Method:
Infrared Controlled Interface Polarization Spectrometer
Measurement Range:
0-100,000 PPM
1-100%
Gas
Display
Range: Auto
Ranging:
Manual
Ranging:
PPM:
0-10,000 PPM
scale:
0-10,000
%
Gas:
1-100% %
Gas:
0-100%
Sensitivity:
0-1000 PPM: 1 PPM
1000-10,000
PPM:
5
PPM
1-100%
Gas:
0.5%
Accuracy:
Greater of +/- .5% or +/- 10% of reading (typical, std conditions)
(% Gas on manual mode)
Detection Alarms Modes:
Digital Methane Detection (DMD):
Audible tone when detection threshold is exceeded
Adjustable Alarm Level from 1 to 9000 PPM
Tick:
Continuous audio tone relative to concentration
System Fault Warning:
Audible tone and indication on the display
Self-Test & Calibration:
Built in Self-Test and Calibration function verifies operation and
adjusts calibration for maximum sensitivity. Test gas cell integrated
within
the
instrument.
Compliance:
EN
61326-1
Conducted Emissions Class B
EN 61326-1
Radiated Emissions Class B
EN 61000-4-2 4kV/8kV
ANSI
C63.4
Class
B
EN
61000-4-3
3
V/M
FCC 47 CFR Part 15 Class B
Dust Filter:
Replaceable filter provides dust protection. Easy change out quick
disconnect filter cap.
Display:
Large easy to read backlit LCD (.75” Numeric)
Operating Temperature:
0 to + 122° F (-17 to 50° C) (nominal battery voltage)
Humidity:
5 to 95% RH, non-condensing
Enclosure:
IP54 (Water splash and Dust resistant)
Instrument Weight:
5.6 lbs.
Carrying Case:
13 lbs. empty; 21 lbs. filled
24.5” x 21” x 9”
Power Supply:
Internal rechargeable Li-ion battery or
External 12 VDC car battery with optional power conditioner
Battery Operating Life:
8 hours at 32° F with out backlight on
Battery Charger:
External, in-line, 110 - 240 VAC, 50/60 hertz. 10 hours to 90%
charge
Shoulder Strap:
Single over the shoulder padded strap
Speaker Volume:
108 dBs @ Alarm port (A-fast)
Survey Probe:
Quick connect fitting with locking clasp. Adjustable length from
25”
to
41”
Bar hole Probe:
Std: 20”; Optional 36”
Intrinsic Safety:
Class 1 Division 1 Group D T3
UL
913
MetLab
#E112840
CHAPTER I
DP-IR System Specifications