ENMET ISA-44-RALE-OD User Manual
Page 16
ENMET Corporation
ISA-44RALE-OD/ISA-44RAHE-OD/ISA-44E-OD
12
Figure 4: Interior Terminal Enclosure
Table 3: Wiring Information Terminal Enclosure
For ISA-44RALE-OD / ISA-44E-OD (when Purge and Horn are supplied)
Terminal
Enclosure
Connection
Signal
TB5-6
MOS Sensor Ground
TB5-7
MOS Sensor Heater
TB5-8
MOS Sensor Signal
TB5-2
CO High Alarm Relay, Common
TB5-1
CO High Alarm Relay, Normally Open
TB6-1
CO High Alarm Relay, Normally Closed
TB5-5
CO Low Alarm Relay, Common
TB5-4
CO Low Alarm Relay, Normally Open
TB5-3
CO Low Alarm Relay, Normally Closed
TB6-2
Oxygen Alarm Relay, Common
TB6-3
Oxygen Alarm Relay, Normally Open
TB4-1
AC Ground
TB4-2
110 V
AC
(black)
TB4-3
110 V
AC
(white)
NOTE: The terms "normally open" and "normally closed" correspond to the de-energized positions of the relay contacts.
The relays are energized during normal (non-alarm) channel operation, so the "normally open" position is closed
and the "normally closed" position is open during non-alarm channel operation. The relays are de-energized
during alarms or when power to the channel is interrupted.