beautypg.com

Warning – Dunkirk WPSB Series II User Manual

Page 25

background image

25

EQUIPMENT AND OPTIONAL ACCESSORIES

WARNING

Burn and scald hazard. Safety relief valve could

discharge steam or hot water during operation.

Install discharge piping per these instructions.

!

SAFETY RELIEF VALVE
Safety relief valve is required on your boiler. Water expands

as it is heated. If there is no place for water to expand

into, water pressure will build up inside boiler and system.

Should this happen, safety relief valve will automatically

open at predetermined pressure. This will relieve the strain

on boiler and system. Run pipe from relief valve outlet

(pipe must be same size as outlet and open end must not

be threaded) to open drain, tub or sink, or other suitable

drainage point not subject to freezing. Failure to do so may

cause water damage or injury should safety relief valve

release.

EXPANSION TANK
Expanding water fl ows into expansion tank. Tank should

be correct size. Tank is fi lled with air. As water expands it

compresses air in the tank to form air pressure cushion.

This “spring-like” cushion serves to maintain correct

operating water pressure regardless of water temperature.

This assures “full measure” of water, even in highest

radiation unit of system. It also prevents blowing off of

safety relief valve. Air in tank in beginning (with system

fi lled with cold water) is suffi cient for proper operation.

Tank also serves as trap for excess air in system. Air

would cause gurgling in pipes and in effi cient circulation in

radiators if left in system.
It is possible for tank to become “waterlogged” (fi lled with

water). It can also become overfi lled with air. This can hap-

pen after fi lling system with new water. Fittings provided on

tank and in line to tank are for bleeding off excess water or

air.
When installing this tank, it is important:

1.

Tank be higher than boiler top.

2.

Pipe to tank continuously rises up to tank (so air

can “bubble” up to it).

DIAPHRAGM TYPE EXPANSION TANK
Diaphragm type expansion tank takes place of conventional

expansion tank. Carefully read instructions packed with

your tank assembly.
Tank comes with 10-12 pounds per square inch air charge.

This is the same as pressure produced in system by automat-

ic fi ll valve. When system is fi rst fi lled, tank will contain little

or no water.
As water is heated its pressure increases. It expands into

tank, compressing air in tank. Compressed air cushion per-

mits water in system to expand as temperature changes.

Diaphragm type tank can be mounted on air purger fi tting

or at any convenient place in supply or return line.

AIR ELIMINATING FITTING (AIR PURGER)
Air purger is used to remove excess air from system. It

is installed in supply line. It will eliminate air from water

before it reaches radiators and bleed off this air.

MAIN AIR VENT FOR DOWN FLOW SYSTEMS OR

DIAPHRAGM TYPE EXPANSION TANK
Before system is fi lled with water, there is air in pipes and

radiation units. Some of it will be trapped as system is

fi lled . It is possible to eliminate most of this air through

air vent on radiation units. Main air vent will speed and

simplify this. Install on highest point in supply main when

all radiation is below top of boiler.

AUTOMATIC FILL VALVE
For a safe, effi cient operation, hot water system must be

completely fi lled with water. Adding new water, when

needed can be done manually (by use of hand valve in

water supply line). Requires regular attention to system’s

needs. Automatic fi ll valve accomplishes this without atten-

tion. Install in supply line on hot water boilers only. Valve

operates through water pressure differentials. It does not

require electrical connection.

DRAIN VALVE
Manual valve provides means of draining all water from

boiler and system. It is often installed in 3/4” tapping at

bottom of end boiler section. Or it can be installed in tee

where return line enters boiler.

CIRCULATING PUMP
Every forced hot-water system requires circulating pump.

Separate pump or zone valve is required for each zone,

if you have a two or more zone system. Pump must have

capacity to provide circulation required by your system.

Pump is connected into main just ahead of boiler. It is also

wired to electrical system.

VENT DAMPER
This product is automatic, motorized stack damper

developed to increase effi ciency of heating system by

reducing standby losses from heating apparatus and

conditioned air space. Damper closes chimney vent

when burner is off and fully opens it when combustion is

required.