beautypg.com

Dunkirk WPSB Series II User Manual

Page 12

background image

12

Removing Existing Boiler From Common Venting

System
When an existing boiler is removed from common venting

system, common venting system is likely to be too large for

proper venting of appliances remaining connected to it.
At time of removal of existing boiler, following steps shall

be followed with each appliance remaining connected to the

common venting system placed in operation, while other

appliances remaining connected to common venting system

are not in operation.

1.

Seal any unused openings in the common venting

system.

2.

Visually inspect the venting system for proper size and

horizontal pitch and determine there is no blockage or

restriction, leakage, corrosion and other defi ciencies

which could cause an unsafe condition.

3.

Insofar as is practical, close all building doors and

windows and all doors between the space in which the

appliances remaining connected to the common venting

system are located and other spaces of the building.

Turn on clothes dryers and any appliance not connected

to the common venting system. Turn on any exhaust

fans, such as range hoods and bathroom exhausts, so

they will operate at maximum speed. Do not operate a

summer exhaust fan. Close fi replace dampers.

4.

Place in operation the appliance being inspected. Follow

the lighting instructions. Adjust thermostat so appliance

will operate continuously.

5.

Test for spillage at the draft hood relief opening after

5 minutes of main burner operation. Use the fl ame of

a match or candle, or smoke from a cigarette, cigar or

pipe.

6.

After it has been determined that each appliance

remaining connected to the common venting system

properly vents when tested as outlined above, return

doors, windows, exhaust fans, fi replace dampers and

any other gas-burning appliance to their previous

conditions of use.

CHIMNEY AND VENT PIPE CONNECTION

7.

Any improper operation of the common venting system

should be corrected so the installation conforms with

the National Fuel Gas Code, ANSI Z223.1/NFPA 54.

When re-sizing any portion of the common venting

system, the common venting system should be re-sized

to approach the minimum size as determined using the

appropriate tables in Chapter 13 of the National Fuel

Gas Code, ANSI Z223.1/NFPA 54.

Vent connectors serving appliances vented by natural draft

shall not be connected into any portion of mechanical draft

systems operating under positive pressure.