2 initialation & installation – ADLINK ND-6510 User Manual
Page 55
NuDAM-6521
• 51
5.2 Initialation & Installation
Software Installation
1. If you have already installed “NuDAM Administration” then skip other steps.
2. Backup your software diskette
3. Insert “NuDAM Administration” disc into CD-ROM:
4. Change drive to the path of CD-ROM. For example, your drive of CD-ROM is
F:, then change the drive to F:
5. Find the setup of NuDAM Administration and run it.
6. Please follow the steps of setup program then you can successful to install the
nudism Administration.
Objective of Initializing a Brand-New NuDAM-6521
All NuDAM modules. except NuDAM-6520, 6510, and 6530, in a RS-485
network must have an unique address ID, however, every brand-new
NuDAM-6521 has a factory default setting as following:
♦
Address ID is 01.
♦
Baud rate is 9600 bps
♦
RS-485 Interface
♦
Host Watchdog timer is disable
Therefore, to configure the brand-new NuDAM before using is necessary,
otherwise the address ID will be conflict with others modules because the ID of
new modules are identity . The baud rate may also be changed according to
user‘s requirements.
Default State
The NuDAM I/O modules must be set at Default State when you want to change
the default settings, such as the ID address, baud rate, check-sum status etc.
All NuDAM I/O modules have an special pin labeled as DEFAULT*. The module
will be in Default State if the DEFAULT* pin is shorted to ground when power
ON. Under this state, the default configuration is set as following:
♦
Address ID is 00.
♦
Baud rate is 9600 bps.
♦
RS-485 Interface