OBSERVED PROBLEM

Burner does not light after ODS/

pilot is lit

Delayed ignition of burner

Burner backfiring during com-

bustion

Yellow flame during burner

combustion

Slight smoke or odor during initial

operation

Heater produces a whistling noise

when burner is lit

Heater produces a clicking/tick-

ing noise just after burner is lit

or shut off

REMEDY

1. Clean burner (see Cleaning

and Maintenance, page 13)

or replace burner orifice

2. Contact local propane/LP gas

company

1. Contact local propane/LP gas

company

2. Clean burner (see Cleaning

and Maintenance, page 13)

or replace burner orifice

1. Clean burner (see Cleaning

and Maintenance, page 13)

or replace burner orifice

2. Contact local propane/LP gas

company

3. Replace burner

4. Replace gas regulator

1. Check burner for dirt and

debris. If found, clean burner

(see Cleaning and Mainte-

nance, page 13)

2. Contact local propane/LP gas

company

3. Replace gas regulator

1. Problem will stop after a few

hours of operation

1. Turn control knob to lowest

position and let warm up for

a minute

2. Operate burner until air is

removed from line. Have gas

line checked by local propane/

LP gas company

3. Observe minimum installation

clearances (see Figure 2, page 6)

4. Clean burner (see Cleaning

and Maintenance, page 13)

or replace burner orifice

1. This is common with most heat-

ers. If noise is excessive, contact

qualified service person

POSSIBLE CAUSE

1. Burner orifice is clogged

2. Inlet gas pressure is too low

1. Manifold pressure is too low

2. Burner orifice is clogged

1. Burner orifice is clogged or

damaged

2. Inlet gas pressure is too low

3. Burner damaged

4. Gas regulator defective

1. Not enough air

2. Inlet gas pressure is too low

3. Gas regulator defective

1. Residues from manufacturing

processes

1. Turning control knob to high-

est position when burner is

cold

2. Air in gas line

3. Air passageways on heater

blocked

4. Dirty or partially clogged

burner orifice

1. Metal expanding while heating

or contracting while cooling

TROUBLESHOOTING

Continued