Adams Condensing Oil-Fired Furnace User Manual
Page 16
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

FLUE PRODUCTS
MAKE HOLE HERE
F0RC02 MLASUREME^fT,
SMOKE AND TEMPERATURE
READINGS
SEAL WITH RTVSIUCONE
APPROXIMATELV 18’ABOVE
CENTERLINE OF TEE
DO NOT USE CEMENT
AT METAL COLLAR
STAINLESS/RUBBER
QUICK CONNECT COUPLER
CONDENSATE COLLECTOR
VENT TO ATMOSHPERE
PREFILL TRAP WTH WATER
CONDENSATE NEUTRAUZER
NEUTRALIZER MUST LAY
HORIZONTALLY
REPLACE AT THE BEGINNING
Of EACH HEATING SEASON
TO FLOOR DRAIN
OR CONDENSATE PUMP /¿=
Note:
Furnace
may be
vented from
left OF right
side.
IX. OIL LINE
GENERAL
The furnace rating plate includes the approved
furnace input rating and fuel types. The furnace
must be equipped to operate on the type of oil
applied.
CAUTION I
TO PREVENT UNRELIABLE
OPERATION OR EQUIPMENT
DAMAGE, THE OIL LINE PRESSURE
MUST BE SET AT 140 P.S.I.
OIL TANK
Oil storage tanks must be selected and installed in
compliance with applicable codes; in the United
States, NFPA31.
Standard for the Installation of Oil Burning
Equipment. Chapter 2, and in Canada, CAN/CSA-
B139, Installation Code for Oil Burning Equipment.
Section 6. Observe all local codes and by-lays. In
general, the oil tank must be properly supported and
remain stable in both empty and full conditions. The
oil tank must be fitted with vent and supply pipes to
the outdoors. Refer to the above-mentioned codes
for sizing. The vent pipe must be no less than 1 %
inches I.P.S., and terminate with an appropriate vent
cap in a location where it will not be blocked.
■7
The fill pipe must be no less than 2 inches I.P.S..
and terminate with an appropriate cap In a location
where debris will not enter the fill pipe during oil
delivery.
If located indoors, the tank should normally be in the
lowest level, (cellar, basement, etc.), it must be
equipped with a shut-off valve at the tank outlet used
for the oil supply. The oil tank must be located as to
not block the furnace/room exit pathway. Observe
all clearances specified in the above-mentioned
codes.
PIPING INSTALLATION
In the United States, NFPA 31, Standard for the
Installation of Oil Burninq Equipment. Chapter 2.
In Canada, the entire fuel system should be installed
in accordance with the requirements of CAN/CSA
B139, and local regulations. Use only approved fuel
oil tanks, piping, fittings, and oil filters.
Ensure that all fittings used in a copper oil tine
system are high quality flare fittings. Do not use
compression fittinqs Do not use Teflon tape on any
fittings.
Pressurized or gravity feed installations must not
exceed 3 PSIG. Pressures greater than 10 PSIG
may cause damage to the shaft seal. If the height of
the oil stored in a tank above the oil burner exceeds
11 ^ feet, it may be necessary to use a pressure
regulating device approved for this purpose.
15