Load wiring (section b), Crestron green light™ architectural dimming – Crestron electronic Green Light 120 Volt User Manual
Page 7
![background image](/manuals/72459/7/background.png)
CRESTRON GREEN LIGHT™
Architectural Dimming
Load Wiring (Section B)
CAUTION: Bypass jumpers are provided on each output to allow testing and to protect the module during
installation. The jumper shorts the L, SW and DM terminals so that the load circuit is energized when the branch
breaker is on. Do not remove the bypass jumper until all feed and load wiring has been completed, and the circuits
have been tested for electrical faults.
NOTE: Use copper conductors only – rated 75
°C.
Wire Gauge and Torque Values
TERMINAL
CONNECTOR MAX WIRE RANGE
TORQUE
STRIP LENGTH
LOAD & DM OUTPUTS
26-10 AWG
5.31 lb-in (0.6 Nm) to
7.08 lb-in (0.8 Nm) max
3/8”
(9 mm)
DIM CONTROL
(GLX-DIMFLV8 only)
28-12 AWG
4.43 lb-in
(0.5 Nm)
5/16”
(8 mm)
GROUND BAR
14-10 AWG
35 lb-in
(4.0 Nm)
5/16”
(8 mm)
GROUND LUG
14-4 AWG
45-25 lb-in
(5.1-2.8 Nm)
3/4"
(19 mm)
1. Each output has a label with the number of the controlling circuit breaker printed on it. With the
corresponding circuit breaker turned off, connect the controlled circuit (LOAD) wires to the output per the
markings on the module as shown in the following diagrams. Terminals for load wiring accept one 10 – 14
AWG wire.
Load Wiring for GLX-DIM6, GLX-DIMFLV8, and GLX-HSW8 (Jumper Installed)
TO BRANCH BREAKER
(PREWIRED)
TO NEUTRAL BUS
(PREWIRED)
TO LOAD
JUMPER
(INSTALLED)
GLX-DIM6
GLX-HSW8 AND GLX-DIMFLV8
TO BRANCH BREAKER
(PREWIRED)
TO LOAD
TO NEUTRAL BUS
(PREWIRED)
TO LOAD
(3-WIRE BALLASTS
ONLY)
JUMPER
(INSTALLED)
Installation Guide – DOC. 6688A
CRESTRON GREEN LIGHT Architectural Dimming
• 7