Dimensions, Dimensions ratings and capacities, Eh 450 – Bryant 450D User Manual
Page 2
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

DIMENSIONS
RATINGS AND CAPACITIES
ELECTRICAL CONNECTION
WATER
outlet
'
O
GAS CONNECTION
DIMENSIONS
SIZE
A
B
C
D
E
WATER INLET
WATER OUTLET
36
40-3/8
48
53
5-5/16
15-1/2
1
1
54
46-3/8
56
60
7-1/16
18-3/8
1-1/4
1
MODEL
36-450 D
54-450 D
Cooling Capacity
BTUH
34,000
52,000
Heat Input
BTUH
120,000
180,000
Gas Connection Size
INCHES
1/2
3/4
Condenser Air Delivery
CFM
4,500
6,700
Water Flow (Min. Required)
GPM
7.5
11
Max. Frictional Loss Handled by Chiller Pump
FT HEAD
23
20
Max. Elevation of Coil Above Chiller
FT
22
22
Condenser Fan Motor
115V, 60 Cy., 1 Phase
HP
1/3
1/2
Pump
115V, 60 Cy., 1 Phase
HP
1/8
1/8
Minimum Wire Size*
AWG
14
12
Refrigerant
Type
717
717
Amount
LB
24
42
Approximate Shipping Weight
LB
1044
1544
*NOTE:
Satisfactory
where
distance,
measured
along
wire
path,
between
unit
and
connection
into
main
panel does not exceed 100 ft. Where distances are longer, wire sizes should be increased ac
cordingly.