36D-379 DETAILED COOLING CAPACITIES
Air Entering
Chilled Water
Coil 80° DB
WITH A FLOW RATE OF 7.5 GPM
Outdoor Ambient ° F
Enter Water Temperature of
85
95
105
40
45
50
Entering
Capacity
Capacity
Capacity
Capacity
Capacity
Capacity
CFM
Wet
Btuh
X
1000
Btuh
X
1000
Btuh
X 1000
Btuh
X 1000
Btuh
X 1000
Btuh
X 1000
Bulb
Total
Sensible
Total
Sensible
Total
Sensible
Total
Sensible
Total
Sensible
Total
Sensible
71
39.4
20.3
36.2
19.2
34.6
18.7
45.9
22.7
41.0
20.9
34.2
18.5
1000
67
38.5
24.8
35.1
23.5
33.1
22.8
37.7
24.5
32.7
22.6
25.9
20.1
63
35.3
28.4
31.9
27.0
29.6
26.0
30.4
26.4
25.0
24.2
18.3
18.3
71
39.4
20.9
36.4
19.9
34.8
19.3
48.3
24.0
43.1
22.2
35.9
19.7
1100
67
39.0
25.8
35.7
24.6
33.7
23.9
39.6
26.1
34.4
24.1 ■
27.2
21.5
63
36.3
29.9
32.7
28.4
30.4
27.5
32.0
28.2
26.3
25.9
19.3
19.3
71
39.4
21.4
36.8
20.6
35.2
20.0
50.5
25.3
45.1
23.4
37.6
20.8
1200
67
39.2
26.8
36.0
25.6
34.0
24.9
41.4
27.6
36.0
25.6
28.5
22.9
63
37.0
31.3
33.3
29.8
30.8
28.9
33.5
29.9
27.5
27.5
20.2
20.2
71
39.5
22.0
37.5
21.4
35.6
20.8
52.5
26.5
46.9
24.5
39.1
21.9
1300
67
39.4
27.6
36.2
26.5
34.3
25.8
43.1
29.0
37.4
26.9
29.6
24.2
63
37.6
32.7
33.9
31.2
31.5
30.3
34.8
31.6
28.6
28.6
21.0
21.0
-
71
39.5
22.6
37.9
22.1
36.2
21.5
54.4
27.6
48.5
25.6
40.5
22.9
1400
67
39.4
28.5
36.2
27.3
34.4
26.7
44.6
30.4
38.8
28.3
30.7
25.4
63
38.0
34.0
34.3
32.5
32.0
31.6
36.0
33.2
29.6
29.6
21.7
21.7
O'
O'
CO
о
о
со
со
Q
а.
о
о
"а
о.
<
Notes:
1. Sensible heat capacities shown are based on 80F
entering air at the evaporator.
2. Direct interpolation is permissible. Do not extrapolate.
3. To interpolate:
(a) below 80 F DB, subtract 872 Btuh per 1000 efir. for
each degree below 80 F from the listed sensible
capacity.
(b) above 80 F DB, add 872 Btuh per 1000 efra for
each degree above 80 F from the listed sensible
capacity.
4. Formula:
LDB ■ FDB — Sensible Heat Capacity ^Btuh)
1.08 .X cfm
,
Total r.apacitv fRluh)
-------------4:rx
cL
---------------
where h = Enthalpy (Btu- lb)
о
O)
c
о
JC
U
О
In
to
D
u
5E
*u
Ф
a
00
36D-379 COOLING CAPACITY
36D-379 WATER PRESSURE DROP
Capacity Total, Btuh
36,000
Air Flow, CFM
1200
Ext. S. P., ti. Wg.
.4
Ent. Temp, °F
95
Water Flow, GPM
7.5
Pressure Drop, Ft. Wg.
8.6
Eul. Temp, °F
45
Pressure drop in feet of water at the flow rotes shown
GPM
Pressure Drop
GPM
Pressure Drop
4 *
2.9
7.5
8.6
5 **
4.2
8.0
9.6
6.0
5.8
10.0
14.2
7.0
7.6
* Priming rate for 3/4’‘ vertical drop return,
** Priming rate for 1" vertical drop return.
AIR DELIVERY PERFORMANCE WITH COIL IN PLACE
CFM
External Static Pressure Available*
Hi Tap
1000
.59
1100
.50
1200
.40
1300
.28
140u
22
1500
.15
* At 120 V wiihoiil air fillers.