36D-379 DETAILED COOLING CAPACITIES

Air Entering

Chilled Water

Coil 80° DB

WITH A FLOW RATE OF 7.5 GPM

Outdoor Ambient ° F

Enter Water Temperature of

85

95

105

40

45

50

Entering

Capacity

Capacity

Capacity

Capacity

Capacity

Capacity

CFM

Wet

Btuh

X

1000

Btuh

X

1000

Btuh

X 1000

Btuh

X 1000

Btuh

X 1000

Btuh

X 1000

Bulb

Total

Sensible

Total

Sensible

Total

Sensible

Total

Sensible

Total

Sensible

Total

Sensible

71

39.4

20.3

36.2

19.2

34.6

18.7

45.9

22.7

41.0

20.9

34.2

18.5

1000

67

38.5

24.8

35.1

23.5

33.1

22.8

37.7

24.5

32.7

22.6

25.9

20.1

63

35.3

28.4

31.9

27.0

29.6

26.0

30.4

26.4

25.0

24.2

18.3

18.3

71

39.4

20.9

36.4

19.9

34.8

19.3

48.3

24.0

43.1

22.2

35.9

19.7

1100

67

39.0

25.8

35.7

24.6

33.7

23.9

39.6

26.1

34.4

24.1 ■

27.2

21.5

63

36.3

29.9

32.7

28.4

30.4

27.5

32.0

28.2

26.3

25.9

19.3

19.3

71

39.4

21.4

36.8

20.6

35.2

20.0

50.5

25.3

45.1

23.4

37.6

20.8

1200

67

39.2

26.8

36.0

25.6

34.0

24.9

41.4

27.6

36.0

25.6

28.5

22.9

63

37.0

31.3

33.3

29.8

30.8

28.9

33.5

29.9

27.5

27.5

20.2

20.2

71

39.5

22.0

37.5

21.4

35.6

20.8

52.5

26.5

46.9

24.5

39.1

21.9

1300

67

39.4

27.6

36.2

26.5

34.3

25.8

43.1

29.0

37.4

26.9

29.6

24.2

63

37.6

32.7

33.9

31.2

31.5

30.3

34.8

31.6

28.6

28.6

21.0

21.0

-

71

39.5

22.6

37.9

22.1

36.2

21.5

54.4

27.6

48.5

25.6

40.5

22.9

1400

67

39.4

28.5

36.2

27.3

34.4

26.7

44.6

30.4

38.8

28.3

30.7

25.4

63

38.0

34.0

34.3

32.5

32.0

31.6

36.0

33.2

29.6

29.6

21.7

21.7

O'

O'

CO

о

о

со
со

Q

а.

о

о

о.

<

Notes:

1. Sensible heat capacities shown are based on 80F

entering air at the evaporator.

2. Direct interpolation is permissible. Do not extrapolate.
3. To interpolate:

(a) below 80 F DB, subtract 872 Btuh per 1000 efir. for

each degree below 80 F from the listed sensible
capacity.

(b) above 80 F DB, add 872 Btuh per 1000 efra for

each degree above 80 F from the listed sensible
capacity.

4. Formula:

LDB ■ FDB — Sensible Heat Capacity ^Btuh)

1.08 .X cfm

,

Total r.apacitv fRluh)

-------------4:rx

cL

---------------

where h = Enthalpy (Btu- lb)

о

O)

c

о

JC

U

О

In
to

D

u

5E

*u

Ф

a

00

36D-379 COOLING CAPACITY

36D-379 WATER PRESSURE DROP

Capacity Total, Btuh

36,000

Air Flow, CFM

1200

Ext. S. P., ti. Wg.

.4

Ent. Temp, °F

95

Water Flow, GPM

7.5

Pressure Drop, Ft. Wg.

8.6

Eul. Temp, °F

45

Pressure drop in feet of water at the flow rotes shown

GPM

Pressure Drop

GPM

Pressure Drop

4 *

2.9

7.5

8.6

5 **

4.2

8.0

9.6

6.0

5.8

10.0

14.2

7.0

7.6

* Priming rate for 3/4’‘ vertical drop return,

** Priming rate for 1" vertical drop return.

AIR DELIVERY PERFORMANCE WITH COIL IN PLACE

CFM

External Static Pressure Available*

Hi Tap

1000

.59

1100

.50

1200

.40

1300

.28

140u

22

1500

.15

* At 120 V wiihoiil air fillers.