Style Z (Class A) Module for NAC circuits (CAM)
UL LISTED: For use with the FireLarm 2500
Part No. 345-0234
TRANSIENT PROTECTED
BUILT IN 5.1K END OF LINE RESISTOR
POWER REQUIREMENTS IN ALARM: Approx. 25mA @ 24VDC from control panel notification
appliance circuit
The Model CAM Style Z (Class A) Module is designed to be used with the FireLarm 2500 Fire Control
Panels to convert a single Style Y (Class B) notification appliance circuit to a Style Z (Class A) circuit (one
module is required for each notification appliance circuit). The module is provided with snap track which is
mounted to the cabinet via double-sided foam tape and secured by two #6 sheet metal screws. The
module should be mounted in the area below the main circuit module as shown below so that the
terminals are accessible.
NON-POWER LIMITED SIDE
POWER LIMITED SIDE
POWER LIMITED SIDE
290-0023
CAM
MODULES
USE FOAM TAPE TO MOUNT SNAP
TRACK IN CABINET AND SECURE
WITH TWO #6 SHEET METAL
SCREWS BEFORE MOUNTING CAM
MODULE IN SNAP TRACK
2"
5.5"
1
+
+
3
2
-
-
+
4
-
EXTERNAL
INDICATING
APPLIANCES
RED
BLACK
TO INDICATING
APPLIANCE CIRCUIT
TERMINALS.
REMOVE EOL RESISTOR.
POLARITY SHOWN IS FOR
STANDBY (NON-ALARM)
CONDITION
290-0029
CAM
Figure A-4. CAM Module Location.
Figure A-3. CAM Module Wiring.