Content s – CPG FIRELARM 2500 CPG #2561255 User Manual
Page 18

Content
s
1
2
3
CPG #2561255
F
IRE
L
ARM
2500 Operating Manual
3-4
Table 3-1: Current Requirements.
Module/Device
Standby mA
Alarm mA
2500 with LCD display
2500 without LCD display
CAM (Class A module)
RALCD (Remote Annunciator)
ZDACT (Digital Alarm Communicator)
MBM module
PAM-1 or PAM-2 Relay
170
105
0
95
30
30
15
310*
250
25
115
50
15 (250 momentary)
15
*Includes one zone short circuit current.
Table 3-2: Secondary Power Requirements.
NFPA-72 National Fire Alarm Code
Standby Time
Alarm Time
Local Systems
Auxiliary Systems
Remote Station Systems
Central Station Systems
24 hrs.
60 hrs.
60 hrs.
24 hrs.
5 min.
5 min.
5 min.
5 min.
Table 3-3: Calculation Table.
1 2
3
4 5
6
Module/Device
Qty.
Standby mA Per Unit
Total Standby
Current
Alarm mA Per Unit
Total Alarm
Current
Total mA
Total mA
Convert to A
X 0.001 Convert to A
X 0.001
Total A
Total A
Multiply by hours
from table 2
X
AH for 5 mins.
÷ 12
Total Standby AH
Total Alarm AH
+ Total Standby AH
Total
AH
Efficiency Factor
÷ 0.85
Required
AH
Select a battery such that the battery’s amp hour rating meets or exceeds the
calculated amp hour requirement (44AH maximum).