Piping in the well, Pump, Horizontal piping from well to pump – Sears 390.252158 User Manual
Page 4: Installation, Pump/tank installation
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
INSTALLATION
Piping in the Well
The Shallow Well Water System can be installed on a dug
well, drilled well or with a driven point. In a dug or cased
well, a foot valve and strainer should be installed for easy
priniing. It should be installed five to ten feet below the low
est level to which the water wiU drop while the pump is op
erating (pumping water level). To keep sediment from
clogging the strainer, be sure it is five to ten feet above the
bottom of the well. Before installing the foot valve, make
sure that it works freely.
When using a foot valve, a priming tee and plug as shown in
Figure 1, are recommended.
Priming Plug,
Priming Tee
(User Supplied)
INSTALLATION
Figure I
When installed on a driven point well, your Shallow Well
Water System should have a check valve installed as shown
in Figure 2A.
L
t
Check Valve
Steel Drive Pipe
Drive coupling
Figure 2A
Well point
у Driven point
For a pump at sea level moimted directly over the well, be
sure the total lift fiom the pumping water level to the pump
does not exceed 20 feet. This will be less if the pump is off
set from the well.
The maximum lift of any pump decreases at the rate of about
Г less lift for every 1,000 feet of elevation above sea level.
For example, at Denver, Colorado (Elev. 3,000’) the pump
loses five feet of lift. The maximum depth from which it
would pump water would therefore be 15 feet.
Plastic Pipe
Weil Seal
Coupling
Plastic Pipe
Foot Valve
and Strainer
611 1293
Dug or Cased Well
Figure 2B
PUMP/TANK INSTALLATION
Pump
NOTICE: Use Teflon tape supplied with the pump or Plaslo-
Joint Stik' for making all pipe-thread connections to the
pump itself. To avoid stress-cracking, do not use pipe joint
compounds on the pump.
1. Wrap male pipe threads being attached to pump with
one or two layers of Teflon tape. Cover entire thieaded
portion of pipe.
2. Do not overtighten threaded fittings in the plastic pump.
Be sure you do not try to tighten joint past thread stop
in pump port!
3. If leaks occur, remove fittings, clean off old tape, rcwrap
with two to three layers of tape and remake the con
nection. If joint still leaks, replace the fittings (fittings
may be undersized).
4. Be sure to support all piping connected tQ,thf System.
'Lake Chemical Co., Chicago, Illinois
Horizontal Piping from Well to Pump
When the pump is offset more than 25 feet from the well,
horizontal suction pipe size should be increased to reduce
friction losses. Never install a suction pipe that is smaller
than the suction tapping of the pump.