Table 8 — Dry Coil Air Delivery (Cfm)*
at Indicated External Static Pressure and Voltage
— Horizontal Discharge (Without Filter)
48
V-PH-HZ
MOTOR
SPEED
208 V
230 V or 460 V
in. wg
0.0
0.1
0.2
0.3
0.4
0.5
0.0
0.1
0.2
0.3
0.4
0.5
NLT018, NLT024,
NHT024
208/230-1-60
Lowf,
Med“
Watts
451
427
407
383
365
348
501
477
457
433
415
398
Cfm
1185
1129
1088
1026
979
922
1256
1195
1148
1081
1031
971
HI
Watts
511
483
464
440
420
402
561
533
514
490
470
452
Cfm
1370
1291
1221
1142
1063
1003
1442
1359
1285
1202
1119
1056
NLT030, NMT030
208/230-1-60
Lowf,
Med“
Watts
519
507
492
477
455
431
569
557
542
527
505
481
Cfm
1184
1163
1150
1134
1105
1064
1248
1226
1211
1194
1164
1120
Hi
Watts
620
602
581
559
532
493
670
652
631
609
582
543
Cfm
1443
1414
1376
1329
1279
1197
1519
1489
1449
1399
1347
1261
NHT030, NLT036
NMT036, NLT042
NMT042
208/230-1-60
208/230-3-60,
460-3-60tt
Lowf,
Med“
Watts
560
544
527
505
482
461
610
593
575
500
524
494
Cfm
1515
1452
1389
1308
1227
1105
1597
1530
1464
1378
1293
1164
Hi
Watts
670
650
631
602
573
542
720
701
680
653
625
594
Cfm
1765
1705
1621
1521
1383
1254
1857
1795
1708
1603
1457
1321
NET036, 042
208/230-1-60
208/230-3-60
460-3-60tt
Lowf,
Med“
Watts
873
847
814
785
758
734
987
945
911
877
850
809
Cfm
1717
1690
1645
1597
1550
1496
1979
1922
1859
1802
1734
1667
Hi
Watts
1075
1030
995
960
930
900
1121
1087
1046
1017
981
952
Cfm
2119
2062
1995
1913
1863
1793
2135
2066
1998
1931
1858
1795
NHT036, NVT036
NHT042, NVT042
208/230-1-60
208/230-3-60
460-3-60tt
Lowf,
Med“
Watts
740
700
660
615
580
540
755
725
680
650
610
575
Cfm
1913
1820
1736
1645
1544
1428
1976
1909
1806
1714
1603
1495
Hi
Watts
790
760
720
690
650
610
850
820
780
750
715
675
Cfm
2032
1942
1844
1759
1636
1514
2086
1983
1883
1782
1665
1545
NLT048, NMT048
NHT048
208/230-1-60
208/230-3-60
460-3-60tt
Lowf,
Med“
Watts
770
730
690
650
610
575
810
765
730
695
655
610
Cfm
1945
1880
1796
1708
1611
1508
2061
1970
1892
1813
1704
1580
Hi
Watts
850
810
770
730
690
655
890
855
820
780
750
715
Cfm
2138
2045
1943
1846
1738
1624
2178
2081
1941
1869
1769
1650
NVT048
208/230-1-60
208/230-3-60
460-3-60tt
Lowf,
Med“
Watts
985
950
915
890
860
820
1095
1055
1010
975
935
890
Cfm
1931
1901
1862
1813
1768
1703
2183
2125
2071
2005
1931
1854
Hi
Watts
1220
1165
1130
1080
1035
995
1300
1265
1220
1180
1120
1085
Cfm
2376
2311
2244
2170
2083
2003
2511
2431
2359
2271
2168
2087
NLT060, NMT060
NHT060, NVT060
208/230-1-60
208/230-3-60
460-3-60tt
Lowf,
Med“
Watts
1125
1055
1015
980
940
905
1205
1125
1095
1060
1030
990
Cfm
2184
2125
2063
2000
1938
1880
2285
2225
2163
2106
2045
1980
Hi
Watts
1220
1175
1125
1080
1040
1005
1300
1250
1210
1165
1130
1085
Cfm
2380
2307
2262
2165
2095
2024
2487
2412
2335
2260
2179
2110
*Air delivery values are without air filter and are for dry coil. See Table 10 for wet coil pressure drop.
Deduct field-supplied air filter pressure drop and wet coil pressure drop to obtain external static
pressure available for ducting.
tFactory blower-motor speed setting for heating operation.
‘'Factory blower-motor speed setting for cooling operation.
ttDo not change blower speed settings for units with 460-v (high speed only).
NOTE: Do not operate the unit at a cooling airflow that is less than 350 cfm per each 12,000 Btuh of
rated cooling capacity. Evaporator coil icing may occur at airflows below this point. Water blow-off may
occur at airflows above 450 cfm per 12,000 Btuh of rated cooling capacity
The heating and/or cooling airflow of 208/230-v direct-
drive blower motors can be changed by changing the lead
connections of the blower motor. The motor leads are color-
coded as follows:
black
=high speed
blue
= medium speed
red
=low speed
NOTE: For all 208/230-v direct-drive units, the red motor
lead connected to the heat relay (L) on PCI blower control
determines the heating speed and resulting airflow, and the
blue motor lead connected to the cooling relay (H) on PCI
blower control determines the cooling speed and resulting
airflow. See the unit wiring label.
To change the heating and/or cooling speed of a direct-
drive motor, connect the appropriate color-coded lead at blower
motor connector to speed-tap desired. (See unit wiring
label.)
When installing a 208- or 230-v direct-drive unit that is
factory connected for heating and cooling speeds that are
not the same, and the same speed for both heating and cool
ing is required for a particular application, disconnect red
lead at terminal L of heat relay and connect to terminal MI
on PCI blower control. Connect a field-supplied jumper be
tween terminal L on heat relay and terminal H of cooling
relay. Connect blue lead at blower motor to appropriate speed
tap.
18