Fig. 4 - suggested rigging, Step 5 — connect condensate drain, Table 1 — physical data (cent) – Carrier 48NLT User Manual
Page 5: Do not undersize the tube
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Table 1 — Physical Data (cent)
UNIT SIZE 48
NLT
042
NMT
042
NET
042
NHT
042
NVT
042
NLT
048
NMT
048
NHT
048
NVT
048
NLT
060
NMT
060
NHT
060
NVT
060
NOMINAL CAPACITY (ton)
3Vz
4
5
OPERATING WEIGHT (lb)
496
500
500
550
556
574
580
586
586
604
610
616
616
COMPRESSORS
Quantity______
Reciprocating Hermetic, 3500 Rpm
1
REFRIGERANT*
R-22
REFRIGERANT METERING
DEVICE
AocuRater® Piston
CONDENSER COIL
Rows
FIns/ln.
2
20
CONDENSER FAN
Nominal Airflow (Cfm)
Nominal Speed (Rpm)
Quantlty...Dlameter (In.)
Motor Hp (single-phase)
(three-phase)
2500
3000
3500
EVAPORATOR COIL
Rows
Fins/ln._________
EVAPORATOR FAN
Nominal Cfm
Nominal Speed (Rpm)
Diameter x Width (In.)
Motor Hp (single-phase)
(three-phase)
FURNACE SECTION
Burner Orifice No.
(Qty...drlll size) Natural Gas
Burner Orifice No.
(Qty...drill size) Propane Gas
Pilot Orifice Diameter
(In. ...drill size) Natural Gas
Pilot Orifice Diameter (In.)
Propane Gas
2000
I
3450
V2
3/4
’/2
3/4
3 44
4. 44
4 42
5 44
6 44
3 44
4 44
5 44
6 42
3 44
4 44
5 44
6 42
3 55
4 55
4 54
5 55
6. 55
3 .55
4 55
5 55
6 54
3 55
4 55
5 55
6 54
018 77
009
RETURN-AIR FILTERS (sq ln.)t
Disposable
720
816
960
Cleanable
480
544
640
•Operating charge is iisted on unit namepiate
tRequired fieid-suppiied fiiter areas are based on the iarger of the ARi-rated (Air Conditioning & Refrigeration institute) cooling airflow or the heating airflow at a velocity of 300 ft/min
for disposable type or 450 ft/min for high-capacity type. Air filter pressure drop must not exceed 0 08 in wg
Step 5 — Connect Condensate Drain
NOTE: When installing condensate drain connection be sure
to comply with local codes and restrictions.
The unit disposes of condensate water through a %-in.
NPT drain fitting. See Fig. 2 and 3 for location.
Install a 2-in. trap at the drain fitting to ensure proper
drainage. See Fig. 5. Make sure the outlet of the trap is at
least one-in. lower than the unit drain pan connection to
prevent the pan from overflowing. Prime the trap with
water.
If the installation requires draining the condensate water
away from the unit, connect a drain tube using a minimum
of %-in. OD copper tubing, y4-in. galvanized pipe or %-in.
plastic pipe.
Do not undersize the tube.
Pitch the drain tube
downward at a slope of at least one inch in every 10 ft of
horizontal run. Be sure to check the drain tube for leaks.
UNIT 48
CORNER WT (LB)
A
B
C
D
NLT018
99
126
126
99
NLT024
100
127
127
100
NHT024
101
129
129
101
NLT030
103
132
132
103
NMT030
105
133
133
105
NHT030
106
134
134
106
NLT036
107
136
136
107
NMT036
108
137
137
108
NET036
108
137
137
108
NHT036
117
147
148
118
NVT036
119
148
149
120
NLT042
109
139
139
109
NMT042
110
140
140
110
NET042
110
140
140
110
NHT042
117
147
147
117
NVT042
124
153
154
125
NLT048
128
158
159
129
NMT048
130
159
160
131
NHT048
131
161
162
132
NVT048
131
161
162
132
NLT060
136
165
166
137
NMT060
138
166
167
139
NHT060
139
168
169
140
NVT060
139
168
169
140
Fig. 4 - Suggested Rigging