General description

Technical specification

SX460 is a half-wave phase-controlled thyristor type
Automatic Voltage Regulator (AVR) and forms part of the
excitation system for a brush-less generator.

In addition to regulating the generator voltage, the AVR
circuitry includes under-speed and sensing loss protection
features. Excitation power is derived directly from the
generator terminals.

Positive voltage build up from residual levels is ensured by
the use of efficient semiconductors in the power circuitry of
the AVR.

The AVR is linked with the main stator windings and the
exciter field windings to provide closed loop control of the
output voltage with load regulation of +/- 1.0%.

In addition to being powered from the main stator, the AVR
also derives a sample voltage from the output windings for
voltage control purposes. In response to this sample
voltage, the AVR controls the power fed to the exciter field,
and hence the main field, to maintain the machine output
voltage within the specified limits, compensating for load,
speed, temperature and power factor of the generator.

A frequency measuring circuit continually monitors the
generator output and provides output under-speed
protection of the excitation system, by reducing the output
voltage proportionally with speed below a pre-settable
threshold. A manual adjustment is provided for factory
setting of the under frequency roll off point, (UFRO). This
can easily be changed to 50 or 60 Hz in the field by push-
on link selection.


Provision is made for the connection of a remote voltage
trimmer, allowing the user fine control of the generator's
output.


INPUT

Voltage

Jumper selectable

95-132V ac or

190-264V

ac

Frequency

50-60 Hz nominal

Phase 1

OUTPUT

Voltage

max 90V dc at 207V ac input

Current

continuous 4 A dc

Intermittent 6 A for 10 secs

Resistance

15 ohms minimum


REGULATION

+/- 1.0% (see note 1)


THERMAL DRIFT

0.05% per deg. C change in AVR ambient (note 2)


TYPICAL SYSTEM RESPONSE

AVR response

20 ms

Filed current to 90%

80 ms

Machine Volts to 97%

300 ms


EXTERNAL VOLTAGE ADJUSTMENT

+/-10% with 1 k ohm 1 watt trimmer (see note 3)


UNDER FREQUENCY PROTECTION

Set point

95% Hz (see note 4)

Slope

170% down to 30 Hz

UNIT POWER DISSIPATION

10 watts maximum


BUILD UP VOLTAGE

4 Volts @ AVR terminals


ENVIRONMENTAL

Vibration 20-100

Hz 50mm/sec

100Hz – 2kHz

3.3g

Operating temperature

-40 to +70°C

Relative Humidity 0-70°C

95% (see note 5)

Storage temperature

-55 to +80°C


NOTES
1.

With 4% engine governing

2.

After 10 minutes.

3.

Applies to Mod status F onwards. Generator de-rate may
apply. Check with factory.

4.

Factory set, semi-sealed, jumper selectable

5. Non

condensing.