Dc electrical interconnection – Winco ULPSS20B4W/A User Manual
Page 13
3
20-00
60706-228
DC ELECTRICAL
INTERCONNECTION
**** CAUTION ****
Never run the AC and DC wiring in the same con-
duit.
ASCO 165 UL SWITCH
Your DC connection points in the ASCO 65 UL ATS
are on the terminal block in the upper right hand
corner of the ATS panel. The terminal block (TB7) is
numbered through 9. These terminals will accept
# 22 - # 4 AWG stranded wire. It is recommended
that you use # 6 AWG for distances up to 200 feet.
You need to run four (4) wires from the generator set
to the transfer switch.
WIRE #
PURPOSE
RECOMMEND
COLOR
# 5
Battery Positive
Black
# 1
Battery Negative
White
# 24
Fuel Solenoid
Red
# 22
Start
Orange
These wire colors are a recommendation only. The
wires terminate on TB7 as follows:
WIRE #
COLOR
TB7 TERMINAL
# 5
Black
# 3
# 1
White
# 2
# 24
Red
# 4
# 22
Orange
# 7
Jumpers will need to be installed as follows:
WIRE #
COLOR
TB7 TERMINAL
# 5
Black
# 3 & # 5
# 5
Black
# 5 & # 8
The following is an optional way to interconnect the
Generator and the Transfer Switch. the wires termi-
nate on TB7 terminal as follows:
WIRE #
COLOR
TB7 TERMINAL
# 1
White
# 2
# 24
Red
# 4
# 22
Orange
# 7
The following leads are wire-nutted together:
WIRE #
COLOR
FROM
# 5
Black
Generator
# 5
Black
TB7 # 3
# 5
Black
TB7 # 5
#5
Black
TB7 # 8