Viconics C1016 User Manual
Modulating electric duct heater, Applications, Advanced design and pi control
M:\1_BINDER\21_C1000 SERIES\LIT-C1516-E01.doc 4/7/04
C1015 & C1016
O.E.M. Electronic Thermostat
For Zone Modulating Electric Heat
APPLICATIONS
-
+
+
-
T
24 Vac triggered SSR
Modulating Electric Duct Heater
• Modulating room thermostat for electric heating
devices
• Thermostat for single stage electric duct heater
• Thermostat for electric base board strip
ADVANCED DESIGN AND PI CONTROL
Advanced PI control thermostats provides precise
temperature control and eliminates wasted energy caused
by the typical On / Off cycling in conventional thermostats.
Thus the room occupant is able to reduce the thermostat
setpoint to the lowest comfortable setting. The result is
energy savings ranging from 5% to 10%.
DIMENSIONS
50
90
80
70
60
F
114 mm
32 mm
( 71 mm )
( 71 mm )
2.8"
2.8"
4.5"
1.275"
5
4
3
2
1
7
6
( 83 mm )
3.275"
SECURITY SCREW
FROM BACK
WIRING
BASE
( 71 mm )
2.8"
SCREW TERMINALS
COVER TOP
COVER INSIDE
Specifications and equipment are subject to change without prior
notice
COVERS
Factory standard scale is 50 °F to 90 °F for vertical
mounting. °F & °C scales are available on special order
for horizontal or vertical mounting. The thermostat and the
terminals are an integral part of the cover. The cover
hooks onto the base for easy service and is locked in
place using a security screw.
DAY-NIGHT MODE INPUT ( C1016-01 ONLY )
The C1016-01 has a day / night input and an override
button and night mode led mounted on the thermostat
cover. The night mode, initiated by a remote timer or
computer contact, provides energy savings during
unoccupied periods of up to 10 %, without sacrificing
comfort in occupied rooms. A flashing LED indicator
warns an person in an occupied room that the thermostat
is in Night mode. The occupant may override this
condition locally for 2.5 hours by pressing the button on
the thermostat cover.
OUTPUT FOR ELECTRIC HEAT MODULATION
The thermostats control the room temperature by
modulating directly 24 Vac triggered solid state relays (
SSR ) using a time proportioning control algorithm on a 1
second time cycle.
Ex.:
PI
demand
Time on
Time off
Total
cycle
50 %
½ sec.
½ sec.
1 sec.
25 %
¼ sec.
¾ sec.
1 sec.
This time proportioning output cannot be used on
regular mechanical relays or contactors.
SPECIFICATIONS
Operating
Conditions:
0 °C to 50 °C ( 32 °F to 122 °F )
0% to 95% R.H. non-condensing
Sensor:
Local 47 K NTC thermistor
Resolution:
± 0.1 °C ( ± 0.2 °F )
Control accuracy
(calibrated):
± 0.2 ° C ( ± 0.4 °F )
Ranges:
50 °F to 90 °F Standard
( 10 °C to 32 °C ) Optional
Triac output:
Triac: 30 Vac at ½ A max.
Power:
24 VAC -15%, +10% 50/60 Hz; 2 VA