Viconics C1013 User Manual
Page 2
Viconics Electronics Inc. 9245, Langelier Blvd, St-Leonard, Quebec, Canada H1P 3K9
www.viconics.com
028-0019
LIT-C1013-E01
C1013-02 WIRING
3
4
5
6
7
8
24 Vac
Transformer
120 Vac
Open
Close
Common
Actuator
1 to 2 minutes
timing
Field wired by installer
Change over is automatic ( non adjustable )
If supply temperature is lower than 24 C: Cooling mode
If supply temperature is higher than 25.5 C: Heating mode
3
4
5
6
7
8
24 Vac
Transformer
120 Vac
Open
Close
Common
Actuator
1 to 2 minutes
timing
Transformer ( by others )
24 Vac
120 Vac
Optional wiring schematic for applications where a
transformer is an integral part of reheat system
2
2
Change over sensor
C1013-02
Change over sensor
Single stage reheat
24 Vac relay or
24 Vac N.C. valve
R
Single stage reheat
24 Vac relay or
24 Vac N.C. valve
R
Common
24 Vac
Open
Close
Change over
Reheat
Common
24 Vac
Open
Close
Change over
Reheat
C1013-02 SEQUENCE
50 %
100%
0%
Temperature increase
Device
opened
TRUE
HEATING
SETPOINT
TRUE
COOLING
SETPOINT
DIAL SETPOINT
CENTERED
IN DEAD BAND
Device
closed
Device
on
Device
off
PROPORTIONNAL BAND
3.2 F
DEA D BAND 2.0 F
Temperature increase
TRUE
HEATING
SETPOINT
TRUE
COOLING
SETPOINT
DIAL SETPOINT
CENTERED
IN DEAD BAND
Device
opened
Device
closed
PROPORTIONNAL BAND
3.2 F
DEA D BAND 2.0 F
Device
on
Device
off
50 %
100%
0%
Damper in cooling mode
Damper in heating mode
changeover input active