Viconics C1010 User Manual
C1010 electronic thermostat
HOW TO ORDER
Thermostat
C1010-02
C1011-02 **
C1012-02
C1013-02 **
Tri-state output in cooling mode
z
z
z
z
Tri-state output reverses to heating mode
with change over sensor
z
z
Auxiliary reheat
1 stage
1 stage
** these packages include the auto change over sensor.
C1010
Electronic Thermostat
APPLICATIONS
• VAV and by-pass units control
with modulating tri-
state floating output
ADVANCED DESIGN AND PI CONTROL
Advanced PI control thermostats provides precise
temperature control and eliminates wasted energy caused
by the typical On / Off cycling in conventional thermostats.
Thus the room occupant is able to reduce the thermostat
setpoint to the lowest comfortable setting. The result is
energy savings ranging from 5% to 10%.
DIMENSIONS
50
90
80
70
60
F
114 mm
32 mm
( 71 mm )
( 71 mm )
2.8"
2.8"
4.5"
1.275"
5
4
3
2
1
7
6
( 83 mm )
3.275"
SECURITY SCREW
FROM BACK
WIRING
BASE
( 71 mm )
2.8"
SCREW TERMINALS
COVER TOP
COVER INSIDE
MODULATING TRI-STATE FLOATING OUTPUT
For use with tri-state floating actuator (CW/Off/CCW)
having a 1 to 2 minutes timing per 90° of rotation. This is
a true multi positions modulating output. It gives
performances which is equivalent to more expensive 0 to
10 Vdc type output.
COVERS
Factory standard scale is 10°C to 32°C for horizontal
mounting.
°
F & °C scales are available on special order for horizontal
or vertical mounting. The thermostat and the terminals are
an integral part of the cover. The cover hooks onto the
base for easy service and is locked in place using a
security screw
SPECIFICATIONS
Operating
Conditions:
0 °C to 50 °C ( 32 °F to 122 °F )
0% to 95% R.H. non-condensing
Sensor:
Local 47 K NTC thermistor
Resolution:
± 0.1 °C ( ± 0.2 °F )
Control accuracy
(calibrated):
± 0.2 ° C ( ± 0.4 °F )
Ranges:
50 °F to 90 °F Standard
( 10 °C to 32 °C ) Optional
Outputs:
Isolated Triac: 30 Vac at ½ A max.
Power:
24 VAC -15%, +10% 50/60 Hz; 2 VA
Specifications and equipment are subject to change without prior