Engineering Guide Specs

Viconics Electronics Inc

VH7200 Series Digital PI Humidity Controller

June 2008

Document #028-8018-R00

• Humidistat shall have the following modes of operation that can be selected using the local keypad

(model dependant):

Off

System is disabled

Auto

System will satisfy both Humidification and Dehumidification setpoints

Humidification

System will satisfy the Humidification setpoint only

Dehumidification

System will satisfy Dehumidification setpoint only

• Humidistat shall have the ability to lockout the dehumidification sequence based on outside air

temperature from –40ºF up to 122ºF, -40ºC up to 50ºC (outdoor air temperature sensor required).

• Humidistat shall have the ability to lockout the humidification sequence based on outside air

temperature from –15ºF up to 120ºF, -26ºC up to 49ºC (outdoor air temperature sensor required).

• Humidistat shall have an adjustable maximum number of cycles per hour (under normal control

operation) for the output relay for dehumidification and humidification (for on/off models). The
adjustments range from 3 to 8 cycles per hour.

• Humidistat shall be supplied (without networking interface, BACnet MS_TP network interface, Echelon

Lontalk network interface, Zigbee wireless network interface). BACnet MS_TP versions shall be
provided with Protocol Implementation Conformance Statement or Lonmark approval disclosing all
object/SNVT properties and instance numbers to facilitate the integration process. Echelon-Lontalk
Communicating versions shall be provided with appropriate application files and LNS plug-in as
required free of charge from the manufacturer.

• Humidistat shall utilize EEPROM memory to back up local configuration parameters in the event of

power failure. Humidistats requiring batteries, or have no provisions for retention during loss of power
shall not be acceptable.

• Thermostat shall have two (2) adjustable keypad lockout levels limiting access as follows:

Access Level

System Mode Changes

Setpoint Adjustment

0

Yes access

Yes access

1

No access

No Access

• Humidistat shall have a programmable binary input that can be used for the following local monitoring

capabilities:

DI-1

1. None: No function will be associated with the input
2. Service: A backlit flashing “Service” alarm shall be displayed on the local

humidistat LCD screen when input is energized.

3. Canister: A backlit flashing “Canister” alarm shall be displayed on the local

humidistat LCD screen when input is energized. This input can be tied to a dry
contact output supplied by others.

.

• Humidistat shall be pre-programmed, containing all required I/O to accomplish local humidity control.

• Humidistat shall be provided with intelligent HMI, to which will display services only as are available

as switched through local digital input or network layer such as:

Outdoor air temperature display only enabled when outdoor air temperature sensor is

connected

COM Address and various other parameters when a communication module is

integrated inside the unit.

Humidistat with outdoor reset and proportional high limit shall be Viconics, model

VH7270x1000x

Humidistat with outdoor reset only shall be Viconics, model VH7200A1000x