beautypg.com

Viconics VBZS Engineering Guide Specifications User Manual

Page 12

background image

Economizer Mode and CO

2

Level Control

If the fresh air damper is to be used for both free cooling and CO

2

level control (economizer mode and

CO

2

level control, but without fresh air measurement station), only the Min Pos, Max Pos, Min CO

2

and

Max CO

2

parameters as well as the free cooling sequence will be active.

-

The FA Range parameter should be set to 0 CFM.

-

Set AI1 parameter to CO

2

(0 VDC = 0ppm ; 10VDC = 2000ppm)

-

Min Pos, Max Pos, Min CO

2

and Max CO

2

parameters should be set according to the required

setting.

The highest value between free cooling demand output and
interpolation output for the fresh air setpoint will be the output to
the fresh air damper.

Economizer Mode, CO

2

Level Control and Fresh Air Measurement Station

If the fresh air damper is to be used for both free cooling and CO

2

level control with a fresh air

measurement station, only the Min FA, Max FA, Min CO

2

and Max CO

2

parameters as well as the free

cooling sequence will be active.

-

The FA Range parameter should be set to something other than 0 CFM.

-

Use an air flow transmitter to read fresh air level with AI2 input (0-5 VDC input)

-

Min FA, Max FA, Min CO

2

and Max CO

2

parameters should be set according to the required

setting.

The highest value between free cooling demand output and
interpolation output for the fresh air setpoint based on the CO2
level will be the output to the fresh air damper

Min Pos

Max Pos

Min CO

2

Max CO

2

Current
Fresh Air
Setpoint

Current CO

2

Level

Min FA

Setpoint

Max FA

Setpoint

Min CO

2

Max CO

2

Current

FA Setpoint

Current CO

2

Level