Eutectic ec-10, Boiler, Figure 2. barometric draft regulator location – Slant/Fin EC-10 Installation User Manual

Page 4

background image

EUTECTIC EC-10

4

Sufficient space shall be left clear around the boiler.

the minimum recommended dimensions for providing
easy access around the boiler.

8578N016

20

A

40

22

7/

16

20

20

33

7/8

Boiler A

(in)

EC-13

22

1/4
1/4

EC-14

27

EC-15

32

1/4

EC-16

37

1/4

EC-10

Do not stack items on or box in the appliance within
the required clearances to combustibles.

The figures stated in inches in the drawing below are

CHIMNEY

BOILER

BOILER

PITCH UP
1/4" PER LINEAR FOOT

DO NOT INSTALL DRAFT REGULATOR HERE

BAROMETRIC DRAFT CONTROL
INSTALLED ON VERTICAL RISE

18"

MINIMUM

9"

PITCH UP
1/4" PER
LINEAR FOOT

DOUBLE SWING BAROMETRIC DRAFT
CONTROL INSTALLED ON HORIZONTAL
CONNECTOR

DRILL 1/4" HOLE TO MEASURE
DRAFT,SMOKE,CO % AND STACK
TEMPERATURE

DO NOT INSTALL DRAFT REGULATOR HERE

9"

18"

MINIMUM

2

DRILL 1/4" HOLE TO MEASURE
DRAFT,SMOKE,CO % AND STACK
TEMPERATURE

2

CHIMNEY

Figure 2. Barometric Draft Regulator Location