Carrier 48MA/50ME016-040 User Manual
Page 12

Table 3 — Unit 50ME Electrical Data
UNIT
50ME
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
COMP
NO. 1
COMP
NO. 2
OFM
FLA
IFM
POWER
SUPPLY
Min
Max
RLA
LRA
RLA
LRA
No. 1
No. 2
No. 3
Hp
FLA
MCA
MOCP
016
208/230
187
254
63.6
266
—
—
6.2
6.6
—
5
16.2
109.6
125
460
414
508
28.6
120
3.0
6.6
49.5
60
575
518
632
22.8
96
2.4
5.6
39.6
45
024
208/230
187
254
44.4
170
44.4
170
6.2
6.6
—
7.5
24.2
138.0
150
460
414
508
19.9
77
19.9
77
3.0
11.0
61.9
70
575
518
632
15.7
62
15.7
62
2.4
9.0
49.2
60
028
208/230
187
254
63.6
266
44.4
170
6.2
6.6
—
10
30.8
168.9
200
460
414
508
28.6
120
19.9
77
3.0
13.0
75.8
90
575
518
632
22.8
96
15.7
62
2.4
10.5
60.2
70
030
208/230
187
254
63.6
266
63.6
266
6.2
6.6
—
10
30.8
188.0
200
460
414
508
28.6
120
28.6
120
3.0
13.0
84.5
100
575
518
632
22.8
96
22.8
96
2.4
10.5
67.3
90
034
208/230
187
254
63.6
266
63.6
266
6.2
6.6
6.6
15
46.0
210.8
225
20
61.0
224.6
250
460
414
508
28.6
120
28.6
120
3.0
3.0
15
19.8
94.5
100
20
26.6
100.5
125
575
518
632
22.8
96
22.8
96
2.4
2.4
15
16.0
75.6
90
20
21.3
80.6
100
040
208/230
187
254
80.0
345
80.0
345
6.2
6.6
6.6
15
46.2
247.7
300
20
61.0
261.5
300
460
414
508
39.3
150
39.3
150
3.0
3.0
15
19.8
118.5
150
20
26.6
124.5
150
575
518
632
31.4
120
31.4
120
2.4
2.4
15
16.0
95
125
20
21.3
100
125
LEGEND
COMP — Compressor
FLA
— Full Load Amps
IFM
— Indoor (Evaporator) Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
OFM
— Outdoor (Condenser) Fan Motor
RLA
— Rated Load Amps
NOTE: Condenser fan motor no. 1 is a 208/230-1-60 speed control
motor on all units.
Table 4 — Electric Resistance Heater Data
UNIT
50ME
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
ELECTRIC
HEAT kW
(Unit Total)
HEATING ELEMENTS
PER ZONE MODULE
FLA PER
HEATING ELEMENT
MCA
(Each Circuit)
MOCP
(Each Circuit)
016,024
208/230
43/ 53
57/ 70
87/106
2
2
3
13.0/14.4
17.3/19.2
17.3/19.2
150/166
200/221
150/166
175/175
225/225
175/175
460
53
70
106
2
2
3
7.2
9.6
9.6
83
111
166
90
125
175
575
106
3
7.7
133
150
028,030
208/230
54/ 66
72/ 88
108/132
2
2
3
13.0/14.4
17.3/19.2
17.3/19.2
188/207
250/276
188/207
200/225
275/300
200/225
460
66
88
132
2
2
3
7.2
9.6
9.6
103
138
207
110
150
225
575
132
3
7.7
166
175
034,040
208/230
65/ 79
87/106
129/158
2
2
3
13.0/14.4
17.3/19.2
17.3/19.2
225/249
150/165
225/249
250/250
175/175
250/250
460
79
106
158
2
2
3
7.2
9.6
9.6
124
166
249
125
175
250
575
158
3
7.7
199
200
LEGEND
FLA
— Full Load Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NOTES:
1. Heaters are rated at 230 v, 460 v, and 575 v.
2. Terminal boards provided for heater power wire connections are
suitable for use with copper or aluminum wire.
12