WARNING: When adjusting or replacing cams, be sure to shut off air supply to the positioner.
Otherwise, the positioner might react suddenly and cause damage or injury.

Moniteur

M O N I T E U R D E V I C E S I N C O R P O R A T E D

3 6 C o m m e rc e R o a d , C e d a r G ro v e , N J 0 7 0 0 9 Te l . ( 9 7 3 ) 8 5 7 - 1 6 0 0 F a x ( 9 7 3 ) 8 5 7 - 7 2 8 9

w w w . m o n i t e u r d e v i c e s . c o m

Page 4

Installation and Operating Instructions

Series 40 Positioners

1. Loosen the flange nut on the cam. Match the part of
the cam with "0" marked on it with the center of bearing,
as shown to the right. The span adjusting arm unit
should now be aligned.

2.Tighten the flange nut of cam after setting the cam.

3. After cam installation, proceed to adjust zero and
span. Once this is complete, secure the indicator with
the blot (M3) to the feedback shaft. The position for
indicator should be arranged according in the scale
(0 - 90 degrees) shown on the cover.

Cam and Indicator Adjustment

Wiring Diagrams

4-20 mA
INPUT

1 2

GROUND

+ --

Series 41 Standard

4 - 20 mA input

3 4 5

NC

C

NO

SWITCH 1

6 7 8

NC

C

NO

SWITCH 2

4-20 mA
INPUT

1 2

GROUND

+ --

INPUT

INPUT

Series 41 w / Switches

4 - 20 mA input

4-20 mA
INPUT

1 2

GROUND

+ --

INPUT

4-20 mA
OUTPUT

3 4

+ --

OUTPUT

Series 41 w / Output

4 - 20 mA input and output

Specifications - Current Output

Power Supply Rating

15 - 28 VDC loop power

Recommended

Power Supply

24 VDC

Output Signal

4 - 20 mA

Operating Temperature

-20° to 175

Load Impedance

0 - 10K ohms at 24 VDC

Max. Output

55 mA DC

Linearity

+/- 1.0%

Hysteresis

1.0% of full scale

Repeatability

+/- 0.5% of full scale

Adjustment

Zero and Span in Terminal Box

° F

Specifications - Limit Switches

Contacts

SPDT Form C

AC Rating

5A - 125 VAC / 3A - 250 VAC

DC Rating

1A - 24 VDC

Adjustment

cams with set screws

CAUTION: Always check that the electrical load is within the range stated on the nameplate. Failure
to remain within electrical ratings may result in damage to or premature failure of the electrical
switches, sensors or transmitter electronics.

1 2 3

NC

C

NO

SWITCH 1

4 5 6

NC

C

NO

SWITCH 2

4-20 mA
OUTPUT

1 2

GROUND

+ --

INPUT

Series 40

w / Switch output

GROUND

Series 40

w/ 4-20 mA output