WARNING: I
o prevent fire or explosion, use only
with a certified seal fitting within 18 inches of the position transmitter enclosure.
f indicated on the nameplate: t
M O N I T E U R D E V I C E S I N C O R P O R A T E D
3 6 C o m m e rc e R o a d , C e d a r G ro v e , N J 0 7 0 0 9 Te l . ( 9 7 3 ) 8 5 7 - 1 6 0 0 F a x ( 9 7 3 ) 8 5 7 - 7 2 8 9
w w w . m o n i t e u r d e v i c e s . c o m
Operation
Load Current /
Target Present
Load Current /
Target Absent
DC Rating
AC Rating
Supply
Voltage
Switch Type
Sensor
ELECTRICAL RATINGS
Code
Code
Page 2
Moniteur
Installation and Operating Instructions
VPT Series - Sentinel S3
2.5A / 24VDC, 2A / 48 VDC,
0.5A / 125 VDC, 0.25A / 250 VDC
1A / 24VDC
7A / 24VDC
2A / 24VDC
1A / 24VDC
15A / 250VAC
1A / 120VAC
10A / 250VAC
3A / 120VAC
0.25A / 120VAC
Mechanical - SPDT
Gold Plated - SPDT
Mechanical - DPDT
Tungsten TTL - SPDT
Rhodium TTL - SPDT
1
3
4
2
T
NAMUR
PNP
3 - 15 mA
4 - 100 mA
< 1 mA
< 0.7 mA
5-25 VDC
5-60 VDC
P & F NJ2-V3
P & F NBB3-V3-Z4
8
K
WARNING: Flange Cover Bolts are Custom Captivating, contact Moniteur for
genuine replacements. M5 Flange Bolts of type 316SS with min yield of 91,000 psi
are an acceptable alternative.
See www.moniteurdevices.com or contact Moniteur for electrical ratings on switch types not listed here.
WARNING: Potential Electrostatic Discharge Charging Hazard - Dissipate static
electricity on this device before handling.