LAARS Mascot ll LMC - Install and Operating Manual User Manual
Page 39
Mascot II Boilers and Water Heaters
Page 37
was reached
however the cycle count will
not
increment
any
higher
than 999,999 cycles
Replace controller or adjust the count using blue display
50 Maximum hours count
Control operates correctly,
was reached
however the hours count will
not
increment
any
higher
than 999,999 hours
248 CH outdoor temperature
was invalid
251 CH ODR max outdoor temp-
Confirm outdoor reset
erature setpoint was invalid
settings. An invalid
252 CH ODR min outdoor temp-
adjustment has been
erature setpoint was invalid
made
253 CH ODR min water temp-
erature setpoint was invalid
254 CH ODR temperature range
Increase Outdoor air temp-
Adjust setting to within appropriate range
was too small
erature min and max values
(min. 12°C / 22°F)
to a difference greater than
22°F (12°C)
255 CH setpoint minus ODR
Increase Outdoor water
min water temperature was
temperature min and max
too small (min. 12°C / 22°F)
values to a difference greater
Increase setpoint or
than 22°F (12°C)
decrease min water temp.
565 Heat exchanger T-rise limit
Heat exchanger temperature Check for correct water flow
was exceeded
rise exceed
MISCELLANEOUS
Boiler will not stay lit
Indicates lack of flame signal, Check flame detector wiring; clean / replace flame
check fault code on display
detector
Boiler bangs, knocks, hisses
Insufficient water flow /
Check for proper flow, follow piping guidelines in
pump failure; improper piping manual; replace pump; improper glycol percentage
(see Section 6)
Flame pulsates, venting
Insufficient / improper
Ensure venting complies with
Section 3
noise or has difficulty lighting
venting; dirty burner; air in
gas line; dirty heat exchanger
Table 14. Error Codes.
CODE# PROBLEM
PROBABLE CAUSE
SOLUTION
ALERT CODES