App1, Appendix 1 - error codes (continued), Cont – LAARS NeoTherm NTV (Sizes 399-850 MBTU/h) - Service Manual User Manual
Page 101

91
Service Manual - NeoTherm 500
Appendix 1 - Error Codes (continued)
Code Description
L or H Procedure
26
Internal fault:
Static flame ripple
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
27
Internal fault:
Flame rod short to ground detected
H
Check flame rod - See Section B37.
Internal fault in SOLA controller:
1. Reset module
2. If fault repeats, replace module.
28
Internal fault:
A/D linearity test fails
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
29
Internal fault:
Flame bias cannot be set in range
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
30
Internal fault:
Flame bias shorted to adjacent pin
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
31
Internal fault:
SOLA electronics unknown error
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
32-46 Internal fault:
Safety key 0 through 14
L
Internal fault
1. Reset module
2. If fault repeats, replace module.
47
Flame rod to ground leakage
H
Check flame rod - See Section B37.
Internal fault in SOLA controller: Internal fault
1. Reset module
2. If fault repeats, replace module.
48
Static flame (not flickering)
H
Internal fault
1. Reset module
2. If fault repeats, replace module.
49
24 VAC voltage low/high
H
1. Check the module and display connections.
2. Check the module power supply and make sure that
frequency, voltage and VA meet the specifications. See
50
Modulation fault
H
Internal sub-system fault.
1. Review alert messages for possible trends.
2. Correct possible problems.
51
Pump fault
H
Internal sub-system fault.
1. Review alert messages for possible trends.
2. Correct possible problems.
52
Motor tachometer fault
H
Check the blower. See Section B22.
Internal sub-system fault in SOLA controller:
1. Review alert messages for possible trends.
2. Correct possible problems.
App1
cont.