II - SPECIFICATIONS
(cont.)
DIP SWITCH SETTINGS
DANGER
Do not attempt to adjust dip switch settings from there factory default settings.
Doing so will result in damage to unit, property damage, personal injury or death.
Contact Technical Support for information pertaining to dip switch function.
FACTORY DEFAULT SETTING, RESIDENTIAL UNITS
Natural Gas
Propane Gas
Dip Switch Settings:
Dip Switch Settings:
(SW1)
(SW2)
(SW1)
(SW2)
#1 = Off
#1 = On
#1 = Off
#1 = Off
#2 = On
#2 = Off
#2 = On
#2 = Off
#3 = Off
#3 = Off
#3 = Off
#3 = Off
#4 = Off
#4 = Off
#4 = Off
#4 = Off
#5 = Off
#5 = Off
#6 = Off
#6 = Off
#7 = Off
#7 = Off
#8 = Off
#8 = Off
FACTORY DEFAULT SETTING, COMMERCIAL UNITS
Natural Gas
Propane Gas
Dip Switch Settings:
Dip Switch Settings:
(SW1)
(SW2)
(SW1)
(SW2)
#1 = Off
#1 = On
#1 = Off
#1 = Off
#2 = On
#2 = Off
#2 = On
#2 = Off
#3 = Off
#3 = Off
#3 = Off
#3 = Off
#4 = Off
#4 = On
#4 = Off
#4 = On
#5 = Off
#5 = Off
#6 = Off
#6 = Off
#7 = Off
#7 = Off
#8 = Off
#8 = Off
See page 13 for special dip switch settings base on vent length.