2 lc-208w/lc-208w combination, Wiegand elevator control panel – Keri Systems LC-208 Wiegand Elevator Control User Manual
Page 21
Wiegand Elevator Control Panel
1530 Old Oakland Road, Suite 100
01879-002 Rev. C
San Jose, CA 95112 USA
(800) 260-5265 (408) 451-2520 FAX (408) 441-0309
Web: http://www.kerisys.com E-mail: [email protected]
Page 21 of 24
LC-202W/LC-208W
Quick Start Guide
5.4.2
LC-208W/LC-208W Combination
Perform the following wiring instructions to accommodate an elevator application using two LC-
208W panels (up to 16 floors).
1. Make a complete set of connections to the first LC-208W panel. Refer to Section 5.3 on page 16
for all connections to the LC-208W.
2. Daisy-chain the Data0, Ground, and Data1 reader connections from W-TB-B of the second LC-
208W panel to W-TB-C of the first LC-208W panel. Make the connections per the information
in Table 9 and Figure 13 on page 22.
3. Daisy-chain the TxRx+, TxRx-, and Shield Network Communication connections from W-TB-
B of the second LC-208W panel to W-TB-C of the first LC-208W panel. Make the connections
per the information in Table 10 and Figure 14 on page 23.
4. The floor/relay connections for the second LC-208W are made according to the floor/panel
association. Refer to Section 5.3 on page 16 for all floor/relay connections to the LC-208W.
Power connections are made per the instructions in Section 5.2.4 on page 16.
Table 9: LC-208W to LC-208W Panel Wiring Connections
W-TB-B of Second Panel
W-TB-C of First Panel
Reader Ground (OUT)
Reader Ground (IN)
Data0 (OUT)
Data0 (IN)
Data1 (OUT)
Data1 (IN)
Table 10: LC-208W to LC-208W Panel Network
Communication Wiring
W-TB-B of Second Panel
W-TB-C of First Panel
TxRx - (OUT)
TxRx - (IN)
TxRx + (OUT)
TxRx + (IN)
Shield (OUT)
Shield (IN)