5.1
Connecting Wires - Removing Terminal Blocks
Follow the instructions in Figure 4 when connecting wires to the controller or when removing
terminal blocks from the controller.
Figure 4: Connecting Wires and Removing Terminal Blocks
5.2
LC-202W Wiring Connections
The following connections are made to install the LS-202W Elevator Control panel (see Figure 3 on
page 9).
•
Floor Control Relay via W-TB-A
•
RS-485 Controller Network via W-TB-B (network out) and W-TB-C (network in)
•
Reader/Amplifier Daisy-Chain via TB-B (reader output) and W-TB-C (reader input)
•
Earth Ground and Power via TB-C
5.2.1
Floor Control Relay
The Floor Control Relay is connected to the door controls at the elevator panel. If a controller has
an SB-200 Satellite Board attached to control two floors, connect the lower floor to the A-Floor
Control Relay and connect the higher floor to the B-Floor Control Relay. Make the floor control
relay connections per the information in Table 1 and Figure 5 on page 11.
Table 1: Floor Control Relay
Connection
LC-200W TB-3 Pin
SB-200 TB-7 Pin
Description
1
Normally-Open
2
Common
3
Normally-Closed