2 rs-485 controller network, Wiegand elevator control panel – Keri Systems LC-208 Wiegand Elevator Control User Manual
Page 11
Wiegand Elevator Control Panel
1530 Old Oakland Road, Suite 100
01879-002 Rev. C
San Jose, CA 95112 USA
(800) 260-5265 (408) 451-2520 FAX (408) 441-0309
Web: http://www.kerisys.com E-mail: [email protected]
Page 11 of 24
LC-202W/LC-208W
Quick Start Guide
Figure 5: Floor Control Relay Connection
5.2.2
RS-485 Controller Network
All of the controllers in the elevator network communicate through an RS-485 serial
communication network. Per the RS-485 industry specification, this network must be daisy-
chained, with a total network cable length of no more than 4,000 feet. Make the RS-485 network
connections per the information in Table 2 and Figure 6 on page 12.
NOTE: Do NOT connect earth ground to the RS-485 network cable shield. The LC-200 controller
automatically connects earth ground to the shield at one point on the network. This single
connection minimizes the effects of ground loops that can affect controller performance.
Table 2: RS-485 Controller
Network
TB-1 Pin
Description
1
Tx/Rx Negative
2
Tx/Rx Positive
3
Network Cable Shield