5.
If you are using one extension cord for more than one tool, add the nameplate
amperes and use the sum to determine the required minimum cord size. (See Table
below.)
6.
If you are using an extension cord outdoors, make sure it is marked with the suffix “W-
A” (“W” in Canada) to indicate it is acceptable for outdoor use.
7.
Make sure your extension cord is properly wired and in good electrical condition.
Always replace a damaged extension cord or have it repaired by a qualified electrician
before using it.
8.
Protect your extension cords from sharp objects, excessive heat, and damp or wet
areas.
R EC O M ME N D ED MIN IM U M W IRE G A UG E FOR E X TE N SIO N C O R D S *
(120 VO LT )
NAM EPL ATE
AM PERE S
(At Full Load)
EX TENS IO N CO RD LE NG TH
25
Feet
5 0
Feet
75
F eet
100
Feet
150
F eet
0 – 2.0
18
1 8
18
18
16
2.1 – 3.4
18
1 8
18
16
14
3.5 – 5.0
18
1 8
16
14
12
5.1 – 7.0
18
1 6
14
12
12
7.1 – 12.0
18
1 4
12
10
-
12.1 – 16.0
14
1 2
10
-
-
16.1 – 20.0
12
1 0
-
-
-
* Based on lim iting th e line voltage d ro p to five volts at 150% of the ra ted am peres.