Network configuration – Chatsworth Products RIM-600 User Manual
Page 36

RIM-600 Manual
36
an RJ-45 interconnect cable to connect the RIM-600 Node to the patch panel in room A, and an RJ-
45 interconnect cable from the wall jack in room B to the sensor.
The sensor produces an analog signal which must connect directly to the Host or Node.
The path from the sensor to the RIM-600 unit CANNOT pass through a network Hub or
Switch.
Network Configuration
The RIM-600 Node has a serial port on the front panel which is used to configure network settings
and security options. A dumb terminal or terminal emulation software is required to get online and
set up the configuration. The port is male DTE, so a DB9 female–female null modem cable will be
required. Terminal communication settings must be set to:
n
9600 baud, no parity, 8 data bits, 1 stop bit, no flow control
To get online with the RIM-600 Node, connect your terminal to the serial port and press
RIM-600 Node Unit Version: 4.10
Main Menu
1. Display Network configuration
2. Configure Network settings
3. Display system statistics
4. Reset to factory defaults
5. Network Debug
6. Reboot
7. Logout
Enter option->
To display the present Network Configuration settings select
Option 1. To program the Network
settings select
Option 2. Note that the Node must have network visibility of the Host for the
RIM-600 system to function properly. For Network changes to take effect you must reboot the unit
(option 5). A typical sample is shown below:
Network Configuration
Physical Address
00:07:F9:00:10:18
Parent Host IP address
10.1.2.47
Node IP Address
10.1.4.17
Subnet Mask
255.255.255.0
Default Gateway
10.1.4.1
DNS Server
10.1.2.111
Node name
48th Floor Chicago
Allow remote configuration N
Press any key to return to main menu