Carrier 30HXA,HXC076-186 Water-Cooled and Condenserless Chillers User Manual
Page 24

Table 5B — Compressor Electrical Data, 30HXA Units (cont)
UNIT SIZE
30HXA
NAMEPLATE
V-Hz
(3 Phase)
COMPRESSOR NUMBERS
A1
B1
RLA
LRA
RLA
LRA
186
208/230-60
*
*
*
*
460-60
157.9
1175
157.9
1175
575-60
126.2
940
126.2
940
380-60
191.2
1299
191.2
1299
230-50
*
*
*
*
346-50
*
*
*
*
380/415-50
201.2
1265
201.2
1265
186-WD
208/230-60
349.6
743
349.6
743
460-60
157.9
371
157.9
371
575-60
126.2
297
126.2
297
380-60
191.2
410
191.2
410
230-50
332.3
638
332.3
638
346-50
220.5
439
220.5
439
380/415-50
201.2
400
201.2
400
LEGEND
LRA — Locked Rotor Amps
RLA — Rated Load Amps
WD
— Wye-Delta Start
*Units are shipped with wye-delta start as standard. Across-the-line start is not available.
LEGEND
EQUIP
— Equipment
NEC
— National Electrical Code (U.S.A.)
TB
— Terminal Block
Y-Delta — Wye-Delta Start
XL
— Across-the-Line Start
Field Power Wiring
Field Control Wiring
Factory-Installed Wiring
Fig. 12 — Field Power Wiring
NOTES:
1. Factory wiring is in accordance with NEC. Field modifications or
additions must be in compliance with all applicable codes.
2. Wiring for main field supply must be rated 75° C minimum. Use
copper for all units. Maximum incoming wire size for each terminal
block is 500 kcmil.
24